5.4 Configuration with DIP switches
Some settings can be changed with DIP switches.
Procedure:
a) Turn the Multi on, preferably without load and without AC voltage on the input. The Multi
will then operate in inverter mode.
b) Set the DIP switches as required.
c) Store the settings by moving DIP switch 6 to "on" and back to "off".
5.4.1. DIP switch 1
Default setting: to operate the product with the "On/Off/Charger Only" switch ds 1: "off"
When combined with the Digital Multi Control panel, a VE.Bus Smart dongle, CCGX, Venus
GX or alike, DIP switch 1 should also be in the "off" position.
Setting for operation with a 3-position remote switch: ds 1: "on"
The 3-position switch must be wired to terminal H, see appendix A.
Only one remote control can be connected, i.e. either a switch or a Digital Multi
Control panel.
5.4.2. DIP switch 2 to 6
These DIP switches can be used to set:
- Battery charge voltage and Absorption time
- Inverter frequency
- Search mode
Ds2-ds3: Setting the charge algorithm (For more system settings use VEConfigure)
Absorption
ds2-ds3
voltage
ds2=off
14.4
ds3=off
28.8
(default)
57.6
ds2=on
14.1
ds3=off
28.2
56.4
ds2=off
14.7
ds3=on
29.4
58.8
Absorption
Float
Storage
Time
voltage
Voltage
(hours)
13.8
13.2
27.6
26.4
8
55.2
52.8
13.8
13.2
27.6
26.4
8
55.2
52.8
13.8
13.2
27.6
26.4
5
55.2
52.8
17
Suitable for
Gel Victron Deep
Discharge
Gel Exide A200
AGM Victron Deep
Discharge
Gel Victron Long
Life (OPzV)
Gel Exide A600
(OPzV)
Gel MK battery
Li-ion (LiFePO4)
AGM Victron Deep
Discharge
Tubular plate or
OPzS batteries in
semi-float mode
AGM spiral cell