8.5 Unit Treatment of Setting Change Signals Sent during Duty
Rotation
• During Duty Rotation, both Main unit and Sub unit ignore setting
change instructions sent from remote controller and Comfort
Cloud app.
• If CNT communication error on a unit is detected for more
than 2 minutes, that unit is allowed to accept setting change
instruction from remote controller and Comfort Cloud app. After
communication error is cleared, that unit will start to ignore
setting change instructions.
8.6 Support of Backup Unit during High Set Temperature vs Room
Temperature Difference
Room temperature is detected by the running unit. Upon reaching a
set temperature vs room temperature difference threshold, backup
unit will be turned on or off to support running unit:
For Cool/Dry mode
[(Room temp. – Set temp.)
≥ 2 °C continuously for 60secs] =
backup unit ON
[(Room temp. – Set temp.)
< 0 °C continuously for 60secs] =
backup unit OFF
Temp. (Indoor)
Set Temp.
+2 °C
Set Temp.
OFF
14
Backup Unit
ON
OFF
For Heat mode
[(Set temp. – Room temp.)
≥ 5 °C continuously for 60secs] =
backup unit ON
[(Set temp. – Room temp.)
< 0 °C continuously for 60secs] =
backup unit OFF
Temp. (Indoor)
Set Temp.
Set Temp.
-5 °C
OFF
Time
Backup Unit
ON
OFF
Time