8.3 Unit Response when Error is Cleared during Duty Rotation
• When CNT communication error detected on the running unit is
cleared, the running unit will continue running and the backup
unit will be turned off. Rotation counter will start anew.
• When CNT communication error detected on the backup unit is
cleared, the running unit will continue running and the backup
unit will be turned off. Rotation counter will start anew.
• When system error detected on the running unit or backup
unit is solved, the running unit or backup unit may not turn ON
(Timer LED is still blinking) as the error is still memorised in the
indoor unit. To solve this:
a) Turn off Duty Rotation (Refer to no. 4. Cancelling Duty
Rotation)
b) Go to Quick Menu, and select
clear Timer LED blinking.
Select
c) Turn on Duty Rotation again (Refer to no. 2. Setting Up
Duty Rotation)
8.4 Unit Response after Recovery from Power Breakdown
After recovery from power breakdown:
• Duty Rotation will resume and Main unit will become the
running unit, sub unit will become the backup unit.
• Rotation counter will start anew.
Reset
AC Reset and confirm to