PEHA PHC 940 JRM diag Installations- Und Bedienungsanleitung Seite 2

Phc ausgangsmodul

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Paul Hochköpper GmbH & Co. KG • Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: peha@peha.de • Internet: www.peha.de
Installation- and operating instructions
PHC output modul 940 JRM diag for blinds and roller shutters
8 outputs (2x 4x 1 A) for 4 blinds / roller shutters with diagnosis function
Art.no.: 940 JRM diag
1. Description
The PHC output module 940 JRM diag can control four blinds or roller shutters by
the outputs (O0-O7). The module features within the PHC software four separate
channels for time measurement that can be used independently from the blind/roller
shutter functions as virtual outputs. One channel for time measurement is used for
example under the point „sun sensor delay time measurement" in the roller shutters/
blinds group tools for clocking the sun delay.
The module is divided into 4 groups and features 2 phase connections (I0 a. I1).
The upper phase port supplies the upper 2 output groups with the applied power
supply (230V~/50Hz) and the lower phase port supplies the lower 2 output group.
Two LEDs per output indicate the switched running direction. The green LED signals
„raising  ", the red one signals „lowering ".
2. Connection diagram
N
L L
N
M
M
O0
O1
O2
0 I I
0
O3
M 0
M 1
29
CEBEC
0
1
Jalousie-/Rollladenmodul diag
8 Relaisausgänge für 4 Jalousien/Rollladen
2
3
4A/250V~ ( I max. 2x4x4A / I
max. 2x4x1A)
M
N
N
Art. Nr.: 940 JRM diag
M 2
M 3
O4
O5
O6
I
1 1
I
O7
M
M
N
L
L
N
3. Mounting
The installation of the PHC modules may be carried out by authorised technicians
only. During installation the system's electricity has to be switched off. The PHC mo-
dule is designed for mounting on a 35mm top hat rail acc. EN 50022 in in-/on-wall
distribution housing. The devices can be mounted directly next to each other.
Attention!! The PHC modules may not be employed in connection with devices that
may endanger people, animals or property when operated.
D a t u m
N a m e
The following points must be observed:
Jalousien-/Rolladenmodul
Bearb.
-
the valid laws, standards and regulations
G e p r.
Gehäusebeschriftung
-
the technical state of the art during installation
N o r m
-
the PHC manual and the operating instructions of the PHC modules.
-
Infratec
the fact that operating instructions can only cover general regulations and that
940JRM - GEHB - 01
these regulations must be considered in the context of the PHC system.
Datentechnik GmbH
Format DIN A4H
Urspr.:
Dateiname:
The following systems may not be switched by PHC modules:
-
safety switches such as EMERGENCY OFF
-
emergency power supplies
-
fire alarm systems
-
emergency lighting systems
4 Data connection
The connection between PHC control unit and other PHC modules is established by
the PHC bus line and the modular connectors of the modules. The module connec-
tors are switched parallel in the modules (except in the PHC power supply unit) and
therefore freely selectable as in- or output. Thus the PHC module can be positioned
anywhere in the data line.
A PHC bus line of 30 cm length is included with every PHC module. It is needed for
connecting a neighbouring module or for connecting a module in the next distributor
row. The modules are supplied with voltage by the bus line. Power needs to be
switched off before disconnecting the bus line.
940 JRM diag (Rev05_100115)
GB
Coding switch
Module address
Blatt
1
1
Bl.
126094-04
5. Coding switch
The output module's address is set by the coding switch built into the PHC control
module. The setting of the coding switch is presented in the PHC software under the
menu item „Components g Edit Modules". Make sure that no identical module ad-
dresses are given for PHC output modules. The setting of the coding switch may be
carried out by technicians only. For this the PHC module needs to be switched off and
it must be ensured that there can be no electrical discharge.
6. Current consumption
To calculate the current consumption for the power supply, you should assume a
consumption of 75 mA (internal consumption 10 mA, per relay 8 mA). When a relay
is switched on the current increases to 120 mA for about 2 seconds.
7. Technical data
Art. no.
940 JRM diag
Power supply
Nom. 24 V DC
PHC system (PHC bus)
21-28 V DC (ripple voltage 5 %)
Own consumption
10-75 mA
In-/output module bus
2 modular sockets 6-pin (PHC bus)
Phase connections
Connection for the power supply (230V~/50Hz)
(Terminal I0 u. I1)
for the 2 upper (I0) and 2 lower output group (I1)
Relay outputs
8 outputs (O0-O7) in 4 groups with 2 terminals
(Terminal O0-O7)
clamps ( and ) for loads up to 1 A (230V~/50Hz)
Life-time cycle of relays
> 40,000 switchings with max. load
Coding
DIP switch, 5-pin (Module address)
Ambient temperature
+10° to +50°C
Storage temperature
-20° to +60°C
Screw terminals
max. 2 x 1,5 mm²
Test specifications
EN 60669-2-1
Approbationen
CE KEMA/KEUR CEBEC
Protection level
IP 20
width = 72 mm
Dimensions
height = 55 mm
8. Permitted loads for the relay outputs
Type of load connected
Motor load
9. Warranty
These operating instructions are an integral part of both the appliance and the terms
of warranty. They must be furnished to the user. The technical design of the appliance
is subject to change without prior notification. PEHA products are manufactured using
state of the art technologies in compliance with prevailing national and international
regulations, and are quality tested. If the product should, however, reveal any defects,
PEHA agrees to correct these defects without affecting the rights of the end user to
assert claims against the vendor arising from the purchasing contract, as follows:
If the complaint is justified and properly filed, PEHA can choose to either correct the
defect or supply a functioning product. Claims above and beyond this, or compensation
for follow-on damages are excluded. The appliance is deemed to be justifiably defec-
tive when it is supplied to the end user in an unusable or severely impaired state as a
result of a design, manufacturing or material error. The warranty does not apply to na-
tural wear and tear, improper use, incorrect connection, interference with the appliance
or external impacts. The warranty period runs for 24 months from the purchase of the
appliance by the end user from a vendor, and expires at the latest 36 months after ma-
nufacture of the appliance. The settlement of warranty claims is subject to German law.
Max. output load per output
1 A
GB - 1