Herunterladen Diese Seite drucken

PEHA PHC 940/16AM Installations- Und Bedienungsanleitung Seite 2

Phc ausgangsmodul

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Paul Hochköpper GmbH & Co. KG • Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: peha@peha.de • Internet: www.peha.de
Installation and operating instructions
PHC output modul 940/16 AM
6 relay outputs (6x 16 A)
Art.no.: 940/16AM
1. Description
The 940/16 AM output module serves to switch Ohm-resistive and inductive loads.
The 6 relay outputs (O0-O5) of the output module are potential-free and galvanically
separated from each other.
The module features 6 phase connections (I0 u. I5). The phase connections supply
the relay outputs with the applied power supply (230V~/50Hz).
2. Connection diagram
L L
N
L L
I
0 0 O0 O0
I
I
1 1 O1 O1
I
16 A
16 A
Ausgangsmodul 16A
6 Relaisausgänge
1
6A/250V~
I max. 6x16A
N
I
max. 6x4,5A
M
N
Art. Nr.: 940/16 AM
ON
DIP
16 A
1
2 3 4 5
I
3 3 O3 O3
I
I
4 4 O4 O4
I
L L
N
L L
3. Mounting
The installation of the PHC modules may be carried out by authorised technicians
only. During installation the system's electricity has to be switched off. The PHC
module is designed for mounting on a 35mm top hat rail acc. EN 50022 in in-/on-
wall distribution housing. The devices can be mounted directly next to each other.
Attention!! The PHC modules may not be employed in connection with devices that
may endanger people, animals or property when operated.
The following points must be observed:
N a m e
D a t u m
- the valid laws, standards and regulations
Bearb.
- the technical state of the art during installation
G e p r.
- the PHC manual and the operating instructions of the PHC modules.
N o r m
- the fact that operating instructions can only cover general regulations and that
these regulations must be considered in the context of the PHC system.
Infratec
The following systems may not be switched by PHC modules:
Datentechnik GmbH
- safety switches such as EMERGENCY OFF
Format DIN A4H
Datum
Name
Urspr.:
- emergency power supplies
- fire alarm systems
- emergency lighting systems
4. Data connection
The connection between PHC control unit and other PHC modules is established by
the PHC bus line and the modular connectors of the modules. The module connec-
tors are switched parallel in the modules (except in the PHC power supply unit) and
therefore freely selectable as in- or output. Thus the PHC module can be positioned
anywhere in the data line.
A PHC bus line of 30 cm length is included with every PHC module. It is needed for
connecting a neighbouring module or for connecting a module in the next distributor
row. The modules are supplied with voltage by the bus line. Power needs to be
switched off before disconnecting the bus line.
940-16 AM (Rev05_090923)
N
L L
N
I
2 2 O2 O2
I
16 A
29
CEBEC
Coding switch
Module address
16 A
16 A
I
5
I
5 O5 O5
N
L L
N
16A-Ausgangsmodul
Gehäusebeschriftung
940/16AM - GEHB - 01
Dateiname:
5. Coding switch
GB
The output module's address is set by the coding switch built into the PHC control
module. The setting of the coding switch is presented in the PHC software under the
menu item „Components g Edit Modules".
Make sure that no identical module addresses are given for PHC output modules.
The setting of the coding switch may be carried out by technicians only. For this the
PHC module needs to be switched off and it must be ensured that there can be no
electrical discharge.
6. Switching conditions for voltage switch-on
You can select the switching states OFF, Memory and ON of the relay's from the
PHC output modules on voltage switch-on or recovery in the PHC software under
the menu item "Components g Switch-on Conditions".
The switching conditions are pre-set to "OFF" by the system. The "Memory" swit-
ching condition is selected if, for example, after voltage has been recovered fol-
lowing an interruption of > 50 ms, you want the output module to retain its previous
switching state from the controller.
7. Current consumption
To calculate the current consumption for the power supply, you should assume a
consumption of 60 mA (internal consumption 10 mA, per relay 7 mA). When a relay
is switched on the current increases to 150 mA for about 2 seconds.
8. Technical data
Art. no.
Power supply
PHC system (PHC bus)
Own consumption
In-/output module bus
Phase connections
(Terminal I0 u. I7)
Relay outputs
(Terminal O0-O7)
Life-time cycle of relays
Coding
Ambient temperature
Storage temperature
Screw terminals
Test specifications
Approbationen
Protection level
Dimensions
9. Permitted loads for the relay outputs
Type of load connected
Incandescent lamp
Resistive load
Fluorescent lamps uncompensated
Motor load
Blatt
10. Warranty
1
1
Bl.
These operating instructions are an integral part of both the appliance and the terms
of warranty. They must be furnished to the user. The technical design of the appliance
is subject to change without prior notification. PEHA products are manufactured using
state of the art technologies in compliance with prevailing national and international
regulations, and are quality tested. If the product should, however, reveal any defects,
PEHA agrees to correct these defects without affecting the rights of the end user
to assert claims against the vendor arising from the purchasing contract, as follows:
If the complaint is justified and properly filed, PEHA can choose to either correct the
defect or supply a functioning product. Claims above and beyond this, or compensa-
tion for follow-on damages are excluded. The appliance is deemed to be justifiably
defective when it is supplied to the end user in an unusable or severely impaired
state as a result of a design, manufacturing or material error. The warranty does not
apply to natural wear and tear, improper use, incorrect connection, interference with
the appliance or external impacts. The warranty period runs for 24 months from the
purchase of the appliance by the end user from a vendor, and expires at the latest
36 months after manufacture of the appliance. The settlement of warranty claims is
subject to German law.
126056-04
940/16 AM
Nom. 24 V DC
21-28 V DC (ripple voltage 5 %)
10-60 mA
2 modular sockets 6-pin (PHC bus)
Connection for the power supply (230V~/50Hz)
for the corresponding relay outputs
6 outputs (O0-O5) for loads up to 16 A (230V~/50Hz)
with 2 terminal clamps each and max. switch-on cur-
rent of 120 A (20 ms)
> 22,500 switchings with max. load
DIP switch, 5-pin (Module address)
+10° to +50°C
-20° to +60°C
max. 2 x 1,5 mm²
EN 60669-2-1
CE KEMA/KEUR CEBEC
IP 20
width = 108 mm
height = 55 mm
Max. output load per 16 A output
2500 W
3500 W
18 x 58 W
4,5 A
GB - 1