5

Technical specification

Connection key

OUT3
OUT4
OUT5
AC-N
Nr.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
OUT1
OUT2
PC1001
Label
OUT1
Control signal to compressor relay (230 VAC)
OUT2
Control signal to circulation pump (230 VAC)
OUT3
Control signal to four way valve (230 VAC)
OUT4
OUT5
AC-N
CN1/CN2
NET/GND/12V
DI01/GND
DI02/GND
DI03/GND
Low pressure pressostat signal (digital input)
DI04/GND
High pressure pressostat signal (digital input)
DI05/GND
DI06/GND
Sensor terminal - not used (digital input)
AI01/GND
Sensor terminal - not used (analogue input)
AI02/GND
Incoming water temperature (analogue input)
AI03/GND
Outgoing water temperature (analogue input)
AI04/GND
Evaporator coil temperature (analogue input)
AI05/GND
Ambient temperature (analogue input)
AI06/GND
Sensor terminal - not used (analogue input)
Description
Control signal to fan motor (230 VAC)
Control signal - not used (230 VAC)
Neutral conductor (230 VAC)
Power input (12 VAC)
Display controller
Remote On/Off switch (digital input)
Flow switch (digital input)
Mode input (digital input)
78
HL
GND
AI06
GND
AI05
GND
AI04
GND
AI03
GND
AI02
GND
AI01
CN16