Connection example of 3 doors
Example of a door with 2 readers + electric strike fail close
Door contact
electric strike (fail close)
OUT
IN
Address 1
Address 0
1.The readers for Doors 1.0 and 2.0 must be at address 0 and
those for Doors 1.1and 2.1at address 1.
2. For doors equipped with 2 readers, one must be at address
0 and the other at address 1.
3. The function of OUT1and OUT2can be configured in the
software
4. In1& In2: Connect to GNDby a volt-free contact to activate
the input
5. LIYCYcable, twisted pair, up to 80m.
If more than 80 m. are needed, then termination resistors(120
ohm) may be required at both ends of the RS485line, while
taking into consideration the lengths proposed on our web
site.
6. Alarm cable 2x0,22
7. The cross section of the cable depends on the current
needed by the lock
Note: The elevators relay boards (WS4-RB-12)areconnected
on the same Rs485 lines as the readers.
This product herewith complies with requirements of EMC directive 2014/30/EU.
In addition it complies with RoHS2 directive EN50581:2012
Emergency
button
12V/600mA max
Alarm siren
or
flash siren
Power supply 14,2V
See user manual
12Vbattery
www.xprgroup.com
Box Tamper
Network
Example of a door with 1reader + electric strike fail open
electric strike (fail open)
Push button
12V/600mA max
Example of a door with 1reader + electromagnetic lock
Reader
Address 1
Push button
Electromagnetic Lock 12V/600mA max
Reader
Address 0
Door contact
4