EN | Solar Panel 375W
It is suggested to confirm according to the voltage and current actually used in the power
station.
Grounding:
Although the modules are certified to Safety qualification, grounding is nevertheless to be
used. The grounded connection must be made by a qualified electrician.
Connect module frames to each other using cables with cable lugs.
All the junctions on the conductive connection must be fixed. Soldering is not required.
All ferrous metal in the conductive connection should specially treated, such as by
anodization, spray-painting, galvanization. Stainless steel does not need to be treated.
This protection has been punctured by the grounding device to achieve sufficient
connection.
Wiring
To ensure proper wiring, pay close attention to:
·Correct wiring scheme
When designing the system, avoid forming close loop to minimize risk of an indirect
·The metallic frames must be grounded according to
Article 250 of the U.S. NEC.
·Should provide appropriate engagement through the
anodized layer.
· PV system should work with a reliable lightning
protection system.
1 Stainless steel nut M4
2 stainless steel bolt M4×30
3 stainless steel flat washer M4
4 stainless steel spring washer M4
5 stainless steel serrated washer M4
6 stainless steel slotted washer M4