EGT354F902 | EGT355F902-I
The cable sensor is used to measure temperatures in liquid and gaseous media.
It can be used as a duct sensor and – if installed in an immersion sleeve – as an immersion and
screw-in sensor.

TECHNICAL DATA

Measuring ranges:
–35...+105 °C PVC, LiYY, 2 x 0.25 mm²
–50...+180 °C Silicone, SiHF, 2 x 0.25 mm²
ends stripped with wire end sleeves
T
Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K)
Sensor ⁄ output:
Connection type:
2-wire connection
Testing current:
< 0.3 mA
Protective tube:
made of stainless steel, V4A (1.4571), Ø = 6 mm,
EGT354F902
EGT355F902-I nominal length (NL) = 100 mm
EGT354F902
Connection cable:
EGT355F902-I cable length (KL) = 2.0 m; Silicone, SiHF, 2 x 0.25 mm²
Insulating resistance:
≥ 100 MΩ, at +20 °C (500 V DC)
Process connection:
using immersion sleeves or mounting flange
Permitted humidity:
< 95 % r.H., non-precipitating air
Protection class:
III (according to EN 60 730)
Protection type:
EGT354F902
EGT355F902-I IP 68 (according to EN 60 529)
Type ⁄ Code
Sensor ⁄ Output
EGT354F902
Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K)
EGT355F902-I
Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K)
Ni1000 = +180 °C
max
nominal length (NL) = 50 mm
cable length (KL) = 1.5 m; PVC, LiYY, 2 x 0.25 mm²
IP 65 (according to EN 60 529)
Protective tube
nominal length (NL)
6
Rev. 2021 - V17
1x two-wire connection
Connection cable
cable length (KL)
50 mm
PVC ( 1.5 m )
100 mm
Silcone ( 2.0 m )