CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
• Never fail to have an individual power circuit specifically for the air conditioner. As for the
method of wiring, be guided by the circuit diagram posted on the inside of control cover.
• The screw which fasten the wiring in the casing of electrical fittings are liable to come loose
from vibrations to which the unit is subjected during the course of transportation. Check them
and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of
the wires.)
• Check specification of power source.
• Confirm that supplied electrical capacity is sufficient.
• See to that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
• Confirm that the cable thickness is as specified in the power source specification.
• Always install an earth leakage circuit breaker.
• The following would be caused by voltage drop: Vibration of a magnetic switch, which will
damage the contact point, fuse breaking, disturbance of the normal function of the overload.
• The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.

AIR PURGING

Air and moisture that remain in the refrigerant system, e.g. after installation, can cause undesirable effects
or damage as indicated below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Damage of the compressor.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must always be leak tested and
evacuated with aid of a vacuum pump to remove any noncondensables and moisture from the system.
4
62
All manuals and user guides at all-guides.com
Outdoor unit
Outdoor power supply
220-240V-50HZ
Indoor unit
Indoor power supply
220-240V-50HZ
Fig. 21
One-twin Wiring Diagram
Indoor power supply
220-240V-50HZ