Mounting instructions

General recommendations
The sensor should not be installed near
a heat source.
The sensor should not be installed near
an air discharge grill.
The sensor should not be installed in a
place where it can be directly affected
by the sun.
Install the sensor in an area that
provides proper device ventilation.
Nothing must restrain air circulation to
the sensor.
Suspended ceiling installation
The remote multi-sensor can be mounted
directly into suspended ceiling (Ø 32 mm).
To install the infrared remote
multi-sensor
1. Drill a hole into the suspended ceiling
(Ø 32 mm).
2. Place the infrared remote multi-sensor
in the whole.
Subnetwork communications wiring
The infrared remote multi-sensor can
be freely combined in a daisy chain
configuration (Subnet Adapter is
required to establish a pass-through
connection).
Cable length between each device of
the subnetwork (WTC controller /
Light / Blind expansion modules /
RJ-45 accessories) should not exceed
30 m.
The total max. length of the
subnetwork bus is 180 m.
Note that the End of Line termination
must be set before installing.
3. Screw the rear spring to the infrared
remote multi-sensor.
4. The sensor is now fixed to the
suspended ceiling.