Using the D HP2000
It is important that the D HP2000 be held perpendicular and at a
distance of between 0.5m and 2m from the detector.
1. Switch on D HP2000 by pressing the red power button.
2. Point D HP2000 at detector and press the DOWNLOAD button.
The D HP2000 will confirm the product's identity and call up the
correct menu of parameters and their current settings.
3. Use a combination of UP, DOWN, FORWARD and BACK buttons
to navigate the parameter menu, selecting options for each
shown. (See Tips below.)
4. When options for all parameters have been selected, point the
D HP2000 at the detector and press the UPLOAD button. The
luminaire(s) will switch off briefly during the programming pro-
cess and the D HP2000 shows DATA OK to confirm operation.
5. After a short period of inactivity (default 5 minutes), the D
HP2000 hibernates retaining the most recent settings.
Tips
I. Where there are only two options such as ON/OFF, a double
click of the OK button toggles between them.
II. Where there are multiple options, a double click of the OK button
recalls a list of all options for that parameter. Use the UP, DOWN
and OK buttons to select.
III. Use the OK button to go forward (through the menus) without
displaying help pages.
IV. Press UPLOAD at any time to transfer all current settings from
the handset to the product.

Electrical Connections

Supply
230V
50Hz
Push-to-Make
Retractive Switch
PEHA Lichtsteuerung – PEHA Elektro GmbH & Co. KG a Honeywell Company · Gartenstraße 49 · 58511 Lüdenscheid · Deutschland · www.peha.de · peha@peha.de
L
N
Red
Mains-Rated
TM
OneSwitch
Input
(see overleaf)
Important Additional Notes
1. A means for disconnection must be incorporated in the fixed
wiring in accordance with the current wiring regulations.
2. Although nominally 12V, the dimming output is not SELV and
therefore should be treated with the same respect as mains with
regard to wiring practice. The 0V line of the dimming output is
almost at Neutral potential.
3. The dimming control output should be connected only to the
control input of the ballasts - never to other detectors.
4. This equipment should be used to control only those ballasts
powered from the same phase as the detector.
5. Due to the fact that the photocell is on the ceiling looking down, it
is not possible for measurements made with a lux meter on the
working plane to remain constant when daylight illuminates the
ceiling and the working plane to a differing extent. Therefore, pro-
ducts of this type should be regarded as capable of maintaining an
APPROXIMATE light level only.
115mm
65mm
Brown
Blue
Orange
Polarity-free
Digital Output
White
Grey
MLS
Bus
Violet
W4232E_DE_1204
Seite 6/7