Commissioning Detectors using the D HP2000
It is important that the D HP2000 be held perpendicular and at a
distance of between 0.5m and 2m from the detector.
1. Switch on D HP2000 by pressing the red power button.
2. Point D HP2000 at detector and press the DOWNLOAD button.
The D HP2000 will confirm the product's identity and call up the
correct menu of parameters and their current settings.
3. Use a combination of UP, DOWN, FORWARD and BACK buttons
to navigate the parameter menu, selecting options for each
shown. (See Tips below.)
4. When options for all parameters have been selected, point the
D HP2000 at the detector and press the UPLOAD button. The
luminaire(s) will switch off briefly during the programming pro-
cess and the D HP2000 shows DATA OK to confirm operation.
5. After a short period of inactivity (default 5 minutes), the D
HP2000 hibernates retaining the most recent settings.
Tips
I. Where there are only two options such as ON/OFF, a double
click of the OK button toggles between them.
II. Where there are multiple options, a double click of the OK button
recalls a list of all options for that parameter. Use the UP, DOWN
and OK buttons to select.
III. Use the OK button to go forward (through the menus) without
displaying help pages.
IV. Press UPLOAD at any time to transfer all current settings from
the handset to the product.
Setting the Photocell
The light level should be set at a time when the ambient light level
is equal to the level at which it would be desirable for the photocell
to become active. This can be achieved in the following ways:
1. Wait until the appropriate time of day.
2. Create the desired level by turning lights on or off as required
and/or opening or closing window blinds etc. At this point the
photocell can be commissioned correctly.
Setting the photocell using a D HP10
1. Point the D HP10 at the detector from a distance of about 1m
and press the 'Store' button.
2. The lights will acknowledge the command - i.e. turn on if they
were previously off or briefly turn off, then back on, if they were
on at the start of programming.
PEHA Lichtsteuerung – PEHA Elektro GmbH & Co. KG a Honeywell Company · Gartenstraße 49 · 58511 Lüdenscheid · Deutschland · www.peha.de · peha@peha.de
Setting the photocell using a D HP2000
1. Point D HP2000 at detector and press the DOWNLOAD button.
The D HP2000 will confirm the product's identity and call up the
correct menu of parameters and their current settings.
2. Select UTILITIES, then USER REMOTE.
3. Select SCENE 1 in the display while pointing the D HP2000 at
the detector (as in any programming operation). Press and hold
the OK button until the lights acknowledge the command - i.e.
they either turn on if they were previously off or briefly turn off,
then back on, if they were on at the start of programming.
Setting the photocell using a D HC5
1. Point the D HC5 at the detector.
2. Press and hold the '1' button until the lights acknowledge the
command, i.e. they either turn on if they were previously off
or briefly turn off, then back on, if they were on at the start of
programming.
Note:
In all cases the photocell will make its measurement and store it in
non-volatile memory (i.e. the set-point will be retained in the event
of power loss).
Dimensions
Dimensions
62mm
deep
100mm

Electrical Connections

Electrical Connections
Flange: 10mm deep
Lout
L
N
+ ve
MLS
Bus
-
ve
W4143H_DE_1204