2.2
Intended use
The product is a leak detector for vacuum systems, class I as per EN 13160-
1 and EN 13160-2.
This product may only be used to detect leaks in tanks which are not pres-
surised (i.e. operated under atmospheric conditions) and which are used for
the aboveground or underground storage of liquids.
Tanks
Double-walled steel tanks. The interstitial space must meet the require-
ments as per EN 12285-1 or EN 12285-2
Steel or plastic tanks, double-walled or single-walled with leak protection
lining or leak protection coating, with suitable interstitial space as per
EN 13160-7
The interstitial spaces of the tanks must be operated without leak detection
fluid.
Installation in the manhole of underground tanks is only permissible
with the approval of the authorities.
Liquids
Water-polluting liquids with a flash point > 55 °C, which do not become
viscous and which do not release solid matter
AdBlue® (urea solution 32.5 %) as per DIN 70070
The product must be resistant to the liquid and its vapours. Resistance has
been proven for the liquids listed in the list of substances in chapter "List of
substances".

Information on safety