14 - OPERATION DEFECTS

This paragraph shows some possible operation defects, along
with their cause and applicable remedy.
MAINS led does not switch on
It means that there is no voltage on PD20 control unit card.
1. Before acting on the control unit, disconnect through the
disconnecting switch on the power line and remove the power
supply terminal.
2. Be sure that there is no voltage break upstream the control
unit.
3. Check whether the fuse is burnt-out, if so replace it with same
value.
OVERLOAD led is on
It means that there is an overload on accessory power supply.
1. Remove the extractable part containing terminals M1 to M12.
OVERLOAD led will switch off.
2. Remove the overload cause.
3. Reinsert the terminal board extractable part and check that this
led is not on again.
DESCRIPTION
Test of the safety edges
This menu allows setting the method of control of the safety edges
working
Test disabled
Test enabled for conductive rubber safety edges
Test enabled for optical safety edges
Enabling the ADI device
This menu makes it possible to enable operation of the device connected
to the ADI connector.
Si
PLEASE NOTE: selecting
and pressing MENU accesses the
configuration menu for the device connected to the ADI connector.
This menu is managed by the device itself and is different for each device.
Please refer to the manual for the device.
Si
If the
option is selected, but no device is connected, the display will
show a series of dotted lines.
Exiting the ADI device configuration menu returns to the
Interface disabled, any signals will be ignored
Interface enabled
End of Programming
This menu allows to finish the programming (both default and
personalized) saving the modified data into memory
Do not quit the programming
End of programming
i.Adi
Too long pre-blinking
When a Start command is given and the blinker switches on
immediately but the gate is late in opening, it means that the
setup cycle count down expired and the control unit shows that
service is required.
Slow movement of the gate while closing
This condition can occur when the motor encoder must be
realigned: the gate is closed at slow speed until the closed range
limit and after resumes normal operation.
This anomaly can occur due to power failure with the gate open
or due to other factors related to the malfunctioning of the gate.
Error 1
The following writing appears on display when you exit from
Err1
programming
It means that changed data could not be stored.
This kind of defect has no remedy and the control unit must be
sent to V2 S.p.A. for repair.
Error 2
When a Start command is given and the gate does not open and
the following writing appears on display
This indicates an error in the inverter board operation.
NOTE: If the motor has been heavily used, the motor driver may
have overheated. Let it cool and try again.
- 48 -
DEFAULT
MEMO
no
no
option
no
Err2