4 Unit installation
To install the outdoor unit
1 If necessary, fix the rearmost support beam using lag screws
(accessory E) and washers (accessory F).
2 (Optional) If working with a stony base, use the plugs
(accessory D).
3 Place the outdoor unit on the vibration dampers and connect
them consecutively using the sheet metal washer (accessory J),
spring washer (accessory H), and nut (accessory I).
4.3

Wiring

4.3.1

To prepare the wiring

1 Choose the desired opening in the base frame for the pipes and
electrical wiring.
2 Seal the other openings using the provided base frame sealing
pads (accessory T and U).
INFORMATION
If the cables enter from the bottom, all openings can be
sealed.
3 Fix with M5 Torx screws (accessory A) and washers (accessory
B).
INFORMATION
Tighten them hand-tight (tightening torque <5N∙m).
4.3.2

To position the wiring

1 Insert the small rounded finishing rubber (accessory K) into the
opening through which the cables are passed to ensure the
perfect seal between the opening and pipes and cables.
2 Cut the rounded finishing rubber (accessory K) to the correct
size with a utility knife and place it on the inside of the opening.
3 Place a strip of U-shaped finishing rubber (accessory L) on the
inside of the base frame to prevent damage to the pipes and
cables.
4 Pull the pipes and electrical cables through.
5 Guide the pipes and electrical cables through the floor (base)
entry point of the outdoor unit to prevent kinks in the pipes.
Installation manual
6
a
b
a
d
a
Insulation
b
Refrigerant piping
c
Small rounded finishing profile (accessory K)
d
U-shaped finishing profile (accessory L)
a
Refrigerant piping
b
Cover plate positioned from inside. Placed in 3 positions
(see top view). Pipes are sealed with rubber.
c
Electrical cables