FUNCTIONS FOR THE FACTORY
> 3 sec.
Function
OFS
Thermostat NTC probe offset variation
IrL
Relay hysteresis
Function
T2-1
Change of status from ventilation to cooling
T2-2
Change of status from ventilation to heating
Function
T3-1
Fan ON in heating mode
T3-2
Fan ON in cooling mode
I-T3
T3 probe hysteresis
Function
t1ds
T1 Air probe decompensation - winter cycle (only for set)
F-t1
Fan OFF time
F-t2
ON time of RL2
F-t3
Post-ventilation time
Function
Slu1
Min. speed voltage
SCu2
Med. speed voltage
SHu3
Max. speed voltage
LLSI
Min. speed voltage for autom. fan - winter
HLSI
Max. speed voltage for autom. fan - winter
LLSE
Min. speed voltage for autom. fan - summer
HLSE
Max. speed voltage for autom. fan - summer
PFC
Proportional band in cooling mode
PFH
Proportional band in heating mode
Function
rE-t
General reset and restore default values
NOTE: The Deds, Dedr, Pt1, Pt2, Pt3 functions in the control cannot be applied
This menu allows you to modify the operating parameters of the thermostat,
the electronic motor and other parameters (pump cycle, RESET).
With the control in "OFF" press the M and Fan buttons simultaneously
for 3 seconds.
Select the parameter to be changed by pressing the "+" or "-" buttons and
confirm with the "M" buttons.
Once the parameter has been selected, the display will show the value.
The value can be changed using the "+" or "-" buttons.
Press the "M" buttons once to return to parameter selection; to exit the
menu press the "M" button for more than 5 sec.
THERMOSTAT PARAMETERS - T-MB version only
Description
T2 probe PARAMETERS, CHANGEOVER
Description
T3 probe PARAMETERS, TME minimum probe
Description
Anti-stratification cycle PARAMETERS
Description
THERMOSTAT PARAMETERS - T-MB-ECM version only
Description
OTHER POSITIONS
Description
45
English
Range
Default
± 3 °C
0 °C
0.5 ÷ 2.0 °C
0.7 °C
Range
Default
15 ÷ 25 °C
< 22 °C
25 ÷ 35 °C
> 32 °C
Range
Default
> 30 ÷ 40 °C
> 36 °C
< 10 ÷ 25 °C
< 22 °C
2 ÷ 6 °C
4 °C
Range
Default
0.5 ÷ 2.0 °C
1.5 °C
5 ÷ 13 min.
10 min.
30 ÷ 120 sec.
40 sec.
5 ÷ 240 sec.
60 sec.
Range
Default
1 ÷ 6
1 V
3 ÷ 8
5 V
6 ÷ 10
10 V
1 ÷ 6
1 V
5 ÷ 10
10 V
1 ÷ 6
1 V
5 ÷ 10
10 V
2.0 ÷ 6.0
3.5 °C
2.0 ÷ 6.0
3.5 °C
Operation