Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - Rehau NEA HT 24 V Bedienungsanleitung Und Montageanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 16

Technical data

Nea HT 230 V Nea HT 24 V***
Operating voltage
230 V-AC +/- 10 % 24V-AC + 20 % - 10 %
Max switch current
0 2 A*
Fuse
0 63 A T
Safety**
Class II
Max no of actuators
5 x 3 W
Degree of protection
IP30
Mode of operation
1 Y
Degree of contamination 2
Rated impulse voltage
4 kV
Anfi freeze operation
5 °C
Valve protection function 5 min/week
Dimensions frontside
88 x 88 (mm)
Dimensions backside
75 x 75 (mm)
Depth
26 (mm)
Operating values
6
Storage temperature
-20 to 65 °C
Ambient temperature
0 to 50 °C
Relative humidity
Max 80 %, non condensing
*
Resistive load
** Following proper installation, the requirements of
the protective class will be met.
*** For power supply use a SELV-transformer.
54
All manuals and user guides at all-guides.com
1 A*
1 A T
Class III
37 °C
Insofar as the intended application deviates from that
described in the relevant Technical Information brochure, the
user must consult REHAU and must receive express written
consent from REHAU before commencing this utilization If
the user fails to do so, the sole responsibility for the utilization
shall lie with the individual user In this case, the application,
use and processing of products are beyond our control
Should a case of liability arise, however, this shall be limited
to the value of the goods delivered by us and used by you in
all cases of damage Claims arising from granted guarantees
shall become invalid in the case of intended applications that
are not described in the Technical Information brochures

Werbung