Exhaust air fan Aero_aH 100 with integrated room and cellar dehumidification control
contact openings of at least 3 mm at
each pole.
• The unit may only be operated using
the voltage and frequency shown on
the type plate.
• Do not modify the unit in any way.
• Never operate unit without the
electronics cover [6] and the cover
[4].

5.2. Safe and correct handling

Risk of injury from objects inserted
in the impeller. Do not put any
objects into the device.
Risk of
impeller. Do not stand too close to
the unit to prevent hair, clothing or
jewellery from being pulled into
the unit.
Risks for people (including children) with
reduced
physical,
capabilities or a lack of knowledge. Fan may
only be installed, commissioned, cleaned and
maintained by people who can safely
recognise and avoid the risks associated with
this work. Children must not play with the
unit.
Supply air backflow in the flat
The air flow in the flat must be arranged in
such a way that, as far as possible, no air from
the kitchen, bathroom and lavatory can flow
over into other rooms where the Aero_aH
100 is installed.
A room to be vented must be equipped with
an unclosable, open supply air cross-section
of at least 150 cm², e.g. with the door
ventilation grille MLK.

6. Mounting preparation

6.1. Wall

Observe the minimum distances
to the wall and ceiling, as shown
in the illustration below.
injury
from
rotating
sensory
or
mental
1.
Ensure a level surface around the housing.
2.
Make a wall breakthrough or drill a core hole:
Minimum diameter 105 mm
3.
Lay the mains cable (flush-mounted) up to
the installation location, see the distances
above. When doing so, lead the mains cable
out of the wall by at least 110 mm.
Recommendation: Install wall sleeve
WH 100. Make a wall opening with a
minimum diameter of 115 mm.
For rectangular wall openings, use
mounting plate ZM 11.

6.2. Ceiling

ATTENTION:
Danger of short-circuits damage to
the unit due to condensation in the
fan housing.
Properly insulate ventilation lines thermally.
Plan condensate drainage or a condensate
collector in the rising pipe.
Carry out installation preparations as described in
Chapter 6.1.

6.3. Duct

1.
Deburr inside edged of the pipe.
2.
Carry out installation preparations as
described in Chapter 6.1.
1019-1-0002 Handbuch 31.01.2021_JUSC_Aero_aH100|