Full Programming Options
Delays >
COP delay
MPS delay
TOC delay
Tech IP1 delay
Tech IP2 delay
Hangup delay
Answer delay
AC fail delay
Filt.oride del
BGcall fail
Messages
>
Location
Reassurance
Guidance
Menu Sections
Delays
The delays can be set to alter the length of the delay
before the unit places a call.
COP delay - How long (in seconds) each of the alarm
buttons, in the COP, needs to be pressed before an
emergency call is placed. Default is 3 seconds
MPS delay - 'MPS' refers to Multi Point Station
accessories (part number 492 021). How long (in
seconds) each of the alarm buttons, on the MPS units,
needs to be pressed before an emergency call is
placed. Default is 3 seconds.
TOC delays - how long (in seconds) the alarm button,
in the Memcom
unit (Top Of Car), needs to be pressed
+
before an emergency call is placed. Default is 3
seconds.
Tech IP1 delay - The delay before a technical call is
placed, upon receiving a fault signal from a connected
third party device using the Technical Input.
Tech IP2 delay - The delay before a technical call is
placed, upon receiving a fault signal from a connected
third party device using the Technical Input.
Hang up delay - sets time (in minutes) before Memcom
hangs up a call (talk time).
Answer delay - the number of rings the Memcom
detect before answering any incoming calls. Where
multiple Memcom
+
are sharing a line, they must all have
the same Answer Delay set.
AC fail delay - the delay (in minutes) between a loss of
external power to the Memcom and the corresponding
technical call being placed. If the external power is
restored to the Memcom before the end of the delay
period, the call will be cancelled. Default is 0 minutes.
Filt.oride del - how long (seconds) COP alarm button
needs to be held down after standard COP delay
reached to override door filtering as required by EN81-
28:2018.
BGcall fail - how long (minutes) the Memcom will wait
after failed background call attempt before indicating
failure via pictograms as required by EN81-28:2018.
Messages
Location
This is the only message that needs recording. The location message is
played to the call centre receiving the alarm call, to inform them of the
location of the lift.
Reassurance
This is the message played to trapped passengers as an alarm call is
being placed.
Guidance
If the 'Guided' protocol has been selected, this message will be played
to the call centre operator to ask them to select whether to listen to the
Location message or to be connected to the lift car immediately.
+
must
+
11 11