INSTALLATION

We recommend the system is installed by installation and
heating engineers or electricians.
Professional installation ensures safe long-term operation.
A functional test can be carried out by the district chimney
sweep.
Assembly instructions for window contact (6)
Minimum window opening
These are based on:
a) The power of the exhaust air device in m³/h
b) The size of the window to be opened in m²
c) The size of the window opening in cm (see table 1)
Most kitchens have rectangular tilt and pivot windows.
If your window is round for example, please ask the
AS-5030_I-Manual_150x180_Fin1.indd 15
installation and heating engineers or electrician to calculate
the minimum opening.
The minimum opening of rectangular windows is shown as
an example in the table for the tilt and pivot position.
Calculation table to determine the minimum opening of your
window
1) Determine the extraction power of your exhaust air
extraction device unit in m³/h. You can find the exhaust
air extraction power on the identification plate or in the
operating instructions of your exhaust air device (e.g.
extractor hood).
2) Measure the inner width and height of the window and
calculate the window size in m².
(width x height = m²; e.g. 0.8 m x 1.0 m = 0.8 m²) =
window size
15
ENGLISH | AS-5030
20.08.13 14:48