Fault
The "INPUT" letters on LCD display
section fl ashes
Battery capacity indicator fl ashes
Mains normal, but UPS has no input
Short back up time
UPS doesn't startup after pressing
the ON key
The icon of charger status on LCD
display fl ashes and buzzer beeps
once per second
32 / EN
Table 23
Cause
Anti-connection of mains live and
neutral or mains is out of range
Battery low voltage or battery
disconnected
UPS input breaker open circuit
Battery not fully charged
UPS overload
Battery aged
Didn't press the combination keys
of "on"
UPS has no battery connected or
battery voltage low and too many
loads connected
Fault occurs inside UPS
Charger doesn't work normally or
battery aged
Solution
Re-connect the input power cable
and make a correct connection
Check UPS battery, connect battery
well, if battery damaged, replace it
Press the breaker for reset
Keep UPS connecting with mains
power for more than 8 hours,
recharge battery
Check the usage of loads, remove
some redundant devices
When replace battery, contact
franchiser to get battery and relative
assembly
Press the two keys at the same time
Connect UPS battery well, if battery
voltage low, please turn off UPS and
remove some loads, then start UPS
Contact supplier for servicing
Contact supplier for servicing