FIG 16: The installation for UPS and battery box
The installation between UPS and EBPS can be referred to Fig.16
1. Install the base, then place the RT UPS on the base one by one as Fig.16 shows.
2. The cover installation and cable connection of the UPS and EBPS are the same as RT. (To install the optional EBP
(s) for a UPS)

UPS INITIAL STARTUP

To start up the UPS:
NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
1. If optional EBPs are installed, verify that the EBPs are connected to the UPS.
2. Plug the equipment to be protected into the UPS, but do not turn on the protected equipment.
3. Make any necessary provisions for cord retention and strain relief.
4. Plug the detachable UPS power cord into the input connector on the UPS rear cover.
5. Plug the UPS power cord into a power outlet. The UPS front cover display illuminates.
6. The UPS will do self-test when power on. After that, the charger will charge the battery. If the output displayed on
LCD is "0", there is no output. If you need the UPS output the utility without starting the UPS when plug into the
utility you need to set bPS option to "ON" on the setting mode.
7. Press the combination start up buttons on the UPS front cover for at least half a second. The UPS will start up
and the LED will turn on and off sequentially.
8. Check the UPS front cover display for active alarms or notices. Resolve any active alarms before continuing. See
Troubleshooting". If the indicator is on, do not proceed until all alarms are clear.Check the UPS status from the
front cover to view the active alarms. Correct the alarms and restart if necessary.
9. Verify that the indicator illuminates solid, indicating that the UPS is operating normally and any loads are powe-
red.
10. If optional EBPs are installed, see "Confi guring Battery settings" to set the number of installed EBPs.
11. To change any other factory-set defaults, see "User settings".
NOTE: At initial startup, the UPS sets system frequency according to input line frequency (input frequency
NOTE: At initial startup, the UPS sets system frequency according to input line frequency (input frequency
auto-sensing is enabled by default).
auto-sensing is enabled by default).
NOTE: At initial startup please set the output voltage needed before start up the UPS After the subsequent
NOTE: At initial startup please set the output voltage needed before start up the UPS After the subsequent
startup the UPS will output the setting voltage.
startup the UPS will output the setting voltage.
FIG 17: Long backup external battery connection
1. Battery
2. Black wire
3. Red wire
EN / 13