Output Overload
(Battery Mode)
Voltage Waveform
Harmonic Distortion
Transfer Time
Power Factor
Load Crest Factor
Model
1K - RT
1.5K - RT
2K - RT
3K - RT
208/230/240 Vac Models
Surge Suppression
EMC Certifi cations
EMC (Emissions)
Safety Conformance
Agency Markings
Operating Temperature
30 / EN
108%±5%–150%±5%: Load transfers to Fault mode after 30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after 300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Sine wave
<3% THD on linear load; <5% THD on non-linear load
Online mode: 0 ms (no break)
High Effi ciency mode: 10ms maximum (due to loss of utility)
0.9
3:1
Table 18: Electrical Output Connections (All Models)
Output Connections
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C13-16A)*6
Table 19: Environmental and Safety (All Models)
EN 61000-2-2
EN 61000-4-2, Level 4
EN 61000-4-3, Level 3
EN 61000-4-4, Level 4 (auch für Signalports)
EN 6100-4-5, Level 4 Criteria A
CE per IEC/EN 62040-2,
Class B
Class B
IEC 62040-2:ed2:2005 / EN 62040-2:2006
IEC 62040-1-1, IEC 60950-1
CE
0°C to 40°C (32°F to 104°F) in Online mode, with linear derating for altitude
NOTE Thermal protection switches load to Bypass in case of overheating.
Output Cables
IEC320 C14-10A
IEC320 C14-10A
IEC320 C14-10A
IEC320 C14-10A
IEC320 C20-10A