WITH DIGITAL DISPLAY AND CURRENT/VOLTAGE OUTPUT
GENERAL
The differential pressure transmitters of the DPTE series are
used for measuring differential pressure, positive pressure,
and vacuum. The transmitters are suitable for:
air-conditioning,
building automation,
environmental protection,
valve and flap control,
filter and blower monitoring,
fluid and level monitoring, and
control of air flows.
MODELS
measuring range
order no.
1 (default)
1)
DPTE50SD
-50...0...+50 Pa
1)
DPTE100SD
-100...0...+100 Pa
1)
DPTE500SD
-500...0...+500 Pa
2)
DPTE1000SD
-1 kPa...0...+1 kPa
1)
DPTE100D
0...100 Pa
1)
DPTE250D
0...250 Pa
1)
DPTE500D
0...500 Pa
2)
DPTE1000D
0...1 kPa
3)
DPTE5000D
0...5 kPa
1)
Temperature error at 0...50 °C 5% of full scale (FS)
2)
Temperature error at 0...50 °C 2.5% of full scale (FS)
3)
Temperature error at 0...50 °C 1% of full scale (FS)
® U.S. Registered Trademark
Copyright © 2014 Honeywell Inc. • All rights reserved
DPTExxxxSD / DPTExxxxD
3-WIRE DIFFERENTIAL PRESSURE TRANSMITTERS
overload
burst
capacity
pressure
2
n.a.
20 kPa
40 kPa
n.a.
20 kPa
40 kPa
n.a.
20 kPa
40 kPa
n.a.
40 kPa
70 kPa
1)
0...250 Pa
20 kPa
40 kPa
1)
0...500 Pa
20 kPa
40 kPa
1)
0...1 kPa
40 kPa
70 kPa
2)
0...2.5 kPa
40 kPa
70 kPa
3)
0...10 kPa
60 kPa
120 kPa
PRODUCT DATA & MOUNTING INSTRUCTIONS
FEATURES
Monitoring gaseous, non-aggressive media
Piezo-resistive pressure transducer
Up to 20 kPa (60 kPa) overload capacity
Easy installation and wiring connection
Measurement range adjustable by jumper
Response time adjustable by jumper
Output signal adjustable by jumper
Red digital display
Display of values > +1000 Pa in kPa
Re-zeroing possible by pushbutton
NOTE:
These sensors are not suitable for use in
installations under periodic inspection by the U.S.
Food and Drug Administration.
SPECIFICATION
Supply voltage
Output signal
Response time
Working temperature
Storage temperature
Humidity
Max. current consumption
Linearity + hysteresis error 1.0% of FS
Long-term stability, typical
Repetition accuracy
Orientation dependence
Pressure medium
Process connection
Electrical connection
Fixation of device
Housing material
Cable entry
Protection class
EMV
Weight
18...30 Vac/dc, 50/60 Hz
0...10 Vdc (default) / 4...20 mA
1 s (default) / 100 ms
0...50 °C
-10...70 C
0...95% rh, non-condensing
< 110 mA
0.5% to 2.5% of FS per
year, depending upon measuring
range
0.2% of FS
0.02% of FS
Air + non-aggressive gases
6 mm hose pipe
Screw terminal block for wire
up to 1.5 mm²
With serrated screws
ABS and POM
M20x1.5 (polyamide)
IP54 (with hood), IP00 (without
hood) as per EN60529
EN60770, EN61326
approx. 130 g
MU0B-0616GE51 R0214