Kommunikationsumsetzer 2m
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7XV5662-0AD00/DD, 7XV5662-0AD01/DD
Fast transient bursts,
IEC 60255-26, IEC 61000-4-4 Class IV,
IEEE C37.90.1
High energy surge voltages (SURGE),
IEC 60255-26, IEC 61000-4-5
Auxiliary voltage
Relay outputs
Communication port: RS232/RS485
Communication port: E1/T1
HF on lines, amplitude-modulated,
IEC 60255-26
IEC 61000-4-6 Class III
Power system frequency magnetic field
IEC 61000-4-8, Class IV
IEC 60255-26
Damped oscillatory wave
IEC 61000-4-18
Radiated Electromagnetic Interference
IEEE Std C37.90.2
EMC Tests for Noise Emission (Type Test)
Standard
Radio noise voltage to lines, only auxiliary
voltage IEC-CISPR 11
Interference field strength IEC-CISPR 11
C53000-B1174-C205-2
Downloaded from
www.Manualslib.com
manuals search engine
4 kV, 5 ns/50 ns, 5 kHz
Burst length = 15 ms
Repetition rate 300 ms, both polarities
Ri = 50 Ω, test duration1 min
Impulse: 1.2 μs/50 μs, 10 μs/700 μs
Common mode: 2 kV, 12 Ω, 9 μF
Diff. mode:1 kV, 2 Ω, 18 μF
Common mode: 4 kV, 42 Ω, 0.5 μF
Common mode: 2 kV, 2 Ω, 18 μF
Common mode:
(1.2 μs/50 μs) 4 kV, 2 Ω, 18 μF
(1.2 μs/50 μs) 4 kV, 2 Ω, 18 μF
10 V, 150 kHz to 80 MHz, 80 % AM, 1 kHz
30 A/m continious, 300 A/m for 3 s
2.5 kV (Peak), 100 kHz, 40 pulses per s,
Test duration 60 s, Ri = 200 Ω
20 V/m, 80 MHz to 1 GHz, 80 % AM
35 V/m, 80 MHz bis 1 GHz, 100 % PM
IEC/EN 61000-6-4
150 kHz to 30 MHz limit class A
30 MHz to1000 MHz limit classA