Functions:
Calibration (Press Cal Key for 3 Seconds):
enter
cal
Set Point (Press Set Key):
esc
set
Press Cal and Set Key (both) for 5 Seconds and run Program Setup:
enter
cal
prog
esc
set
Save and escape Program setup with ESC key
Priming Pump Keep Press UP Key for 1 seconds and priming redox pump
Priming Pump Keep Press Down Key for 1 seconds and priming pH pump
Lock pump function
The unit doses in proportional mode respect at Set Point (
10 minutes time period dosing)
Note: The unit in program menu to go out in automatic mode after 1 minutes of wait time, the unit doesn't save nothing.
0000136904
Downloaded from
www.Manualslib.com
Select the calibration routine pH or Redox by Up or Down key.
o
Standard Routine calibration pH probe is 7 and 4 buffer solution and Redox 465 mV buffer
o
solution
Press Set Key and choose SetPoint and adjust value with Up or Down Key before press
o
Enter and confirm.
§ Sp_750mv___700_mv_
Sp_7.4ph____7.6_ph_
§
Program_Menu
o
Language_
§
Redox_Measure
§
setpoint___750_mv
possible to adjust from 0 to 1000 mV value for Redox
sp_type___low
ofa_time_000_min
alarm_band__000_rx
Type__PROP
ph_Measure
§
setpoint____7.4ph
possible to adjust from 0 to 14 pH value.
sp_type___acid
ofa_time_000_min
alr_band__000_ph
Temp__25*C_
measure only.
Type__PROP
Flow_
§
(Adjust value with enter and up or down key Enable or Disable)
It's possible to enable(ON) or disable (OFF) signal input
Calibration_probe
§
Password
§
Exit______save
(Adjust value with up or down key and confirm with enter key)
o
priming_____700mv
o
priming_____7.2ph
o
Press Up and Enter (both) after 5 second flash
o
Press Down and Esc (both) after 5 second flash
o
manuals search engine
Instruction Setting
(Press Enter to set the following Item)
(It's possible to have 5 language EN, IT, SP, DE, FR)
(Adjust value with enter and up or down key) It's
(Adjust value LOW or HIGH)
(Adjust value OFF or set Time)
(Adjust value from 100 to 300 mV )
(Adjust value between OFF, PROP or ON/OFF )
(Adjust value with enter and up or down key) It's
(Adjust value ACID or ALKA)
(Adjust value OFF or set Time)
(Adjust value from 1 pH to 3 pH)
(Adjust value with enter and up or down key) pH
(Adjust value between OFF, PROP or ON/OFF )
(Adjust value with enter and up or down key)
Full
§
(pH 7 and 4, Redox 465 mV buffer solution)
Easy
§
(pH 7, Redox 465 mV buffer solution)
Off
§
(Disabled)
(Adjust value with enter and up or down key, standard value 0000)
Rx_Stop
pH_Stop
minimum distance 25%, maximum distance 90% of
rev. 2.0
enter
cal
press again to unlock
press again to unlock
2