Definitive limitation of the minimum
output position
Using the "manual output control" function,
reduce the burner output to the minimum
output. If necessary, limit the minimum
output position, in the same way as for the
maximum output.
Specific function: ignition checking.
If the ignition position has been modified, it
is possible to carry out a new burner start-
up to check the new ignition position,
without having to quit the settings menu.
To do this, after modifying the ignition
position, position the cursor on the
symbol, and initiate the new start-up using
the
Closing the "Setting the flame" menu.
The burner setting is now complete. If
necessary, it is possible to again correct
each of the settings values. To do this,
position the cursor on the value to be
modified, using the button
Otherwise, at all times, the following
possible ways of closing the "Setting the
flame" menu are available:
- Either restart the burner setting procedure,
passing through the presetting phase
(without entering a password). To do this,
position the cursor on the symboland
confirm with the button
values already saved therefore remain
available. This is essential for testing a new
ignition position.
- Saving the fixed values and ending the
setting procedure. To do this, position the
cursor on the symboland
button
operate and can now be controlled by the
boiler regulation.
- Quitting the settings menu without
reaching the end of the setting procedure.
To do this, position the cursor on the symbol
servomotor positions saved up to this point
are recovered by calling up the settings
menu again.
20
www.ecoflam­burners.com
key.
or
. All the settings
confirm with the
. The burner is then ready to
and confirm with the button
.
. All the
Operating mode ­ Display of the
operating status, the flame signal and
the operating time.
After setting of the burner has been
completed, it switches to operating mode.
The current operation of the burner
(operation at minimum or maximum power)
is indicated by the cursor.
The lower cell shows the intensity of the
signal. The display range is from 0 μA to 7
μA. For a good quality signal is one above
7μA. The following limit values are valid:
• When checking an unwanted flame: the
signal must be < 0.7μA.
• During the safety time: the signal must be
> 1.0μA.
• During operation: the signal must be >
8μA.
The cell at the bottom right displays the
current operating time of the burner.