Instructions for reversing the main coil from left to right on horizontal fancoil units:
A. Unscrew the four Ø 3.9x9.5 screws.
B. Remove the main drip tray, moving it in the direction of the arrow "2". Unscrew the four Ø 3.9x9.5 screws "3" supporting the coil from the left and
right shoulders.
C. Slightly incline the coil towards the arrow "4" and move it away from the left-hand shoulder in the direction of the arrow "5".
D. Reverse the direction of the coil from pos.6 to pos.7.
E. Open the relative pre-punched holes in the opposite shoulder "8" . Insert "9" the coil, inclined as shown in the figure, and fit the hydraulic unions
into the new holes.
F. Tighten the 4 Ø 3.9x9.5 screws in the aligned shoulder-coil bracket holes "10" in the left and right shoulders.
G. Put back the panel "11" taking care to respect the distance of 96.5 mm as shown in the figure.
H. Tighten the four Ø 3.9x9.5 screws "12". Close the open holes in the left-hand shoulder "13" with closed-cell insulating tape".
Instructions for reversing the main coil from right to left on horizontal fancoil units:
to reverse the coil, follow the above instructions but starting from the right-hand shoulder and not the left-hand one.