5.2

Technical data

Max. volume flow
Max. delivery head
Speed
Mains voltage
Rated current
Frequency
Electrical connection
Insulation class
Protection class
Power consumption P
1
Power consumption P
2
Permitted ambient temperature
Approved fluids
Admissible fluid temperature
Maximum permitted operating pressure
Max. permissible inlet pressure
Nominal diameters
Connection replenishment valve on the
break tank FLA Compact-1
Connection replenishment valve on the
break tank FLA Compact-2
Pressure pipe connection FLA Compact-1
Pressure pipe connection FLA Compact-2
Break tank
Material
Ambient temperature
Float switch (protection against low water
level; overflow signal transmitter)
Max. switching voltage
Max. switching current
Max. switching capacity
Material
Protection class
Further data...
Diaphragm pressure vessel

5.3 Scope of delivery

• Fire-extinguishing system Wilo-FLA Compact
(system with switchgear, pump(s) and break tank)
• Installation and operating instructions for the fire-
extinguishing system Wilo-FLA Compact
• Installation and operating instructions for the
pumps
• Installation and operating instructions for the
control device
• Factory acceptance test certificate
(in accordance with EN10204 3.1.B)
• Installation plan (if applicable)
• Electrical circuit diagram (if applicable)
• Installation and operating instructions for the
signal transmitter (if applicable)
• Spare parts list (if applicable)
• Additional documentation for special versions
(if applicable)
26
See catalogue/data sheet
See catalogue/data sheet
2800 – 2900 rpm
3~ 400 V ±10 % V (L1, L2, L3, PE)
See rating plate
50 Hz
F
IP54
See rating plate of pump/motor
See rating plate of pump/motor
5 °C to 40 °C
Pure water without settling sediments
3 °C to 50 °C
On the pressure side 10/16 bar (DS8 to PN 10; DS16 to PN 16)
See inlet pressure fresh water
G2 (Helix V 16.. / Helix V 22..).
2 x G 2 (Helix V 1612 / Helix V 22..).
R 1½ (Helix V 1604 - 1611)
R 2 (Helix V 1612 / Helix V 22..)
R 2½ (Helix V 1604 - 1611)
R 3 (Helix V 1612 / Helix V 22..).
Polyethylene (PE-HWU) black
Filled +5 °C to +40 °C
Empty -20 °C to +60 °C
48 V
0.5 A
3 W / 3 VA
PVC
IP67
8 l (see rating plate diaphragm expansion tank)

5.4 Accessories

• Flexible connection pipes
• Compensators
• Threaded flange
• Diaphragm expansion tank
• Flushing apparatus kit in accordance with
Accessories must be ordered separately as
required. The accessories from the Wilo range
include the following:
DIN 1988-600
WILO SE 07/2019

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Fla compact-1 helix v1604 ds8Fla compact-2 helix v2208 ds16Fla compact-1 serieFla compact-2 serie

Inhaltsverzeichnis