Fault diagnosis
Fault
Urinal flushing
constantly
S. 77
Possible cause
Solenoid valve not
operating correctly
Fault rectification
Make sure that the connected
water line is opened only after
the urinal control system has
been started for a minimum of
30 seconds (make the power
connection).
Make sure that the solenoid valve
is connected to the controller.
Check cable connection.
Check the functioning of the
solenoid valve (diagnostics mode,
see separate operating instructions
or check via app).
Make sure that the solenoid valve
is integrated in the water circuit
with the correct flow direction
(marked on the valve housing).