OPERATING CURVE
mbar
1.25
1
0.75
0.50
0.25
-0.15
These indicate the power in kW depending on the back pressure in mbar in the combustion chamber.
PRESSURE CURVES/GAS DELIVERY
BASIC GAS TRAIN
1
Legend
1 Interception cock with tightness capacity of 1 bar and
load loss ≤ 0.5 mbars.
2 Antivibration coupling.
3 Gas pressure point for pressure measurement.
4 Gas filter.
5 Gas pressure regulator.
6 Gas minimum pressure control device (pressure switch).
0
10
20
2
3
4
5
Pi
30
40
3
6
7
8
3
M
M
7 Safety solenoid valve class A. Closing time Tc ≤ 1".
8 Safety solenoid valve class A. Closing time Tc ≤ 1".
9 Gas delivery adjustment device, normally included in
the solenoid valve 7 or 8.
10 Combustion head.
11 Air minimum pressure control device (pressure switch).
- 24
-
kW
50
9
3
10
11
R
Pt

Werbung