Product specific data
Shutdown detection
Reboot function
Load sensor
Timer function
Relay
The service life of the batteries is app. 4...5 years at +20 °C and will decrease by half with each temperature increase of 10 °C according
to EUROBAT.
Backup time UPSI-2406DP1
Load
3.00 A (100 %)
2.25 A (75 %)
1.50 A (50 %)
0.75 A (25 %)
Unless otherwise specified, the values apply to measurements at +25 ° C
Backup time depends on battery capacitance, load and temperature.
At very high or low temperatures a reduction of backup time occurs.
Via load sensor
Reboot function and time can be configured by software
Configurable via UPSI HID-Battery-Parameter software
(download at www.bicker.de)
UPS shuts down after 15 sec, if connected load decreases below set
value and UPS is being in battery mode
Configurable via UPSI HID-Battery-Parameter software in steps of
single seconds (3600 sec max)
Dry contact on power fail
(Normal mode: open / Backup mode: closed)
Relay switching current max 0.5 A @ 125 V AC / 1 A @ 24 V DC
Power
Duration
72 W
~20 min
54 W
~28 min
36 W
~44 min
18 W
~89 min