How to calibrate the Domestic Ventilation unit
Introduction
Before you can get full benefit of the Ventilation unit, you need to calibrate it.
Calibration
Follow the steps below to calibrate the airflows in the unit according to the values
stated in the specific Service Manual for the unit:
Step
1
2
3
4
5
Airflows
This table can be used to note the airflows.
Action
Press
and
at the same time and keep
them pressed for 5 seconds to activate installer
mode.
Supply Air: Press
and keep it pressed while you
press
to increase the speed of the supply fan.
Alternatively press
to decrease the speed.
Exhaust Air: Press
and keep it pressed while
you press
to increase the speed of the return fan.
Alternatively press
to decrease the speed.
Press
and
at the same time and keep them
pressed for 5 seconds to leave installer mode.
Note the measured airflows on the front of the
ventilation unit and/or in the table below.
Result
The two green LEDs
will flash and the unit
is in calibration mode
The speed of the
supply air will be
increased/decreased
The speed of the
exhaust air will be
increased/decreased
The green LEDs will
turn off and the unit
is out of calibration
mode