Troubleshooting

The CO
transmitter is not field repairable. In the event
2
the unit is not functioning properly, identify the
symptoms and determine a solution:
1. Verify that the unit is mounted properly.
2. Verify that all wiring is correct.
3. Verify that the power supply voltage level is
20 to 30 VAC or 18 to 30 VDC.

Technical Specifications

CD-W00-x0-2 Series Wall Mount CO
CO
Measuring Range
2
CO
Accuracy Across Temperature
2
Range
Long-Term Stability
Response Time (0 to 63%)
Platinum Temperature Sensor
Operating Temperature Range
Storage Temperature Range
Operating Humidity Range
Transmitter CO
Output Signal
2
Resolution of Analog Outputs
Recommended External Load
Power Supply Range
Power Consumption
Current Consumption
Warm-Up Time
Dimensions (H x W x D)
Shipping Weight
Compliance
United States
Europe
Canada
Australia and
New Zealand
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
CD-W00-x0-2 Series Wall Mount CO
If the CO
completing these steps, replace the unit.

Repair Information

If the CD-W00-x0-2 Series Wall Mount CO
Temperature Transmitters fail to operate within their
specifications, replace the units. For a replacement
CO
2
Johnson Controls® representative.
and Temperature Transmitters
2
0 to 2,000 ppm CO
2
68 to 86°F (20 to 30°C): ±(30 ppm +3% of reading)
50 to 68°F (10 to 20°C), 86 to 104°F (30 to 40°C): ±(35 ppm +3.7% of reading)
32 to 50 °F (0 to 10°C), 104 to 122°F (40 to 50°C): ±(40 ppm +4.8% of reading)
±(15 ppm +2% of reading) over 5 years
1 minute
Temperature Sensor: 1,000 ohm, Class F0.15 IEC60751 (Class A), thin-film
platinum
Temperature Coefficient: Approximately 2 ohms per F° (3.9 ohms per C°)
Reference Resistance: 1,000 ohms at 32°F (0°C)
Accuracy: ±0.34F° at 70°F (±0.18C° at 21°C)
32 to 122°F (0 to 50°C)
-40 to 158°F (-40 to 70°C)
0 to 95% RH (noncondensing), 86°F (30°C) maximum dew point
4 to 20 mA and 0 to 10 VDC
Maximum Output Current: 21 mA; Maximum Output Voltage: 11 V
0.3 ppm CO
2
Minimum 1,000 ohms load resistance for 0 to 10 V
Maximum 600 ohm load resistance for 4 to 20 mA
24 VAC ±20%, 50/60 Hz (18 to 30 VDC), Class 2
<1.0W Average, excluding current output consumption
100 mA Peak on AC power; 45 mA Peak on DC power
<1 minute
<10 minutes for full specification
5 x 3-3/16 x 1-1/32 in. (127 x 81 x 26 mm)
0.25 lb (114 g)
UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment,
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
CE Mark - Johnson Controls, Inc. declares that this product is in compliance with
the essential requirements and other relevant provisions of the EMC directive.
UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205-12, Energy
Management Equipment, Industry Canada Compliant, ICES-003
RCM Mark, Australia/NZ Emissions Compliant.