Type D Electronic Control
Control
Light indicators
Blue LED
ON
Indicates that the control is in cooling mode ( ).
Flashing
Indicates that the control is in frost protection
mode ( ).
Red LED (group on the right)
ON
Indicates that the control is in heating mode ( ).
Flashing
Indicates the presence of a fault (sensor failed
or not connected).
Yellow LED ( ) (group on the right)
ON
Indicates that the control is in automatic mode
( ).
Blue LED + Yellow LED
Both ON
Indicates that the control is in automatic mode
( ) - cooling mode ( ).
Red LED + Yellow LED
Both ON
Indicates that the control is in automatic mode
( ) - heating mode (
Red LEDs (group on the left)
ON
Indicates that the fan is operating at the
selected speed.
Yellow LED ( ) (group on the left)
ON
Indicates that the selection of the fan speed is
set automatically.
Red / Blue LED
Flashing
Indicates that the control is in "Autotest" mode.
Green LED ( )
ON
Indicates that the control is in Energy Saving
mode.
Flashing
External contact is open.
"Dip-switch" functions (microswitch)
Dip-switch 1
In open contact position, it permits to activate the frost protection
function ( ).
Dip-switch 2
In open contact position, it permits the fan operation at the selected
Dip-switch 3
In open contact position, it restricts the range of the temperature
selection knob according to the following limits:
Cooling:
minimum selectable temperature: 23°C.
Heating:
maximum selectable temperature: 21°C.
Dip-switch 4
In open contact position, it permits to activate the fan periodically
Dip-switch 5
In open contact position, it permits to activate the Booster Heating
function (additional heating).
Dip-switchs 6, 7 and 8
The position of these dip-switches regulates the control current of
the motor. A higher voltage corresponds to a higher speed of the
fan. The selection is made according to the following table:
Jumper 1 Jumper 2 Jumper 3
Closed
Closed
Closed
Closed
Closed
Open
Closed
Open
Closed
Closed
Open
Open
Open
Closed
Closed
Open
Closed
Open
Open
Open
Closed
Open
Open
Open
GB - 4
).
LOW
MID
HIGH
2V
6V
10V
2V
4V
6V
6V
8V
10V
2V
3V
4V
8V
9V
10V
5V
6V
7V
4V
6V
8V
3V
6V
9V
NOTE:
Factory setting is with all dip-switches in close position.
Use of temperature sensor
Internal sensor: This is used in all installations where the control is
and on the electronic board screenprint.
Remote sensor: This is used on all installations with unitmounted
control. It is positioned on the return air, close to the fan. To
electronic board screenprint.
3
2
1
Fig. A
Internal sensor
NOTE: Factory setting is with activated internal sensor.
Diagnostic warnings
The following alarm situations are indicated:
Possible causes:
Autotest
The autotest function is activated by holding the seasonal
changeover button pressed and at the same time pressing the " "
button three times within 1 second.
In this way it is possible to check the starting of all fan coils. The
Each of the various units will be activated for 10 seconds in the
following sequence:
Low fan speed.
Medium fan speed.
High fan speed.
CV
Motorized cold-water valve.
HV
Motorized hot-water valve.
Fig. 8
3
2
1
Fig. B
Remote sensor
Fig. 9