Herunterladen Diese Seite drucken

Siemens FT2010 series Montage Seite 2

Stockwerkterminal
Vorschau ausblenden Andere Handbücher für FT2010 series:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
en
Intended use
The floor repeater terminal FT2010 enables the fire
detection system to be displayed and operated in a
simplified way. The floor repeater display FT2011
only features display functions. The display on the
FT20xx
is synchronized with stations of the
configured visibility and shows the same event
texts.
Both devices are operated on the FDnet detector
line.
Scope of delivery
The following are included in the scope of delivery:
l
Cover with operating unit
l
Rear panel
l
Inscription strips
l
M 6/40 mm screws
l
M 4.5-6 nylon dowels
Safety instructions
Risk of injury to persons and damage to property
Please observe the following safety instructions:
l
The devices are only intended for stationary installation
in dry rooms.
l
The devices may only be connected to the FDnet
detector line.
l
An external supply must be electrically isolated from
the installation's supply.
Where cables are too thick for the terminal (3), it is
l
possible to install a luster terminal (8) on the rear panel
as a transitory piece.
2
Building Technologies
Fire Safety
Legend
I
Rear panel interior (plastic)
II
Rear panel surface (steel sheet)
III
Cover with operating unit
S
Slits for inscription strips
K
Key switch
1
Breakout openings for cables (5 pcs.)
2
Three mounting holes for wall mounting
3
X101 connector with 8-pin terminal
4
Holes for cam-locks (2 pcs.) of rear panel
5
Cam-locks for mounting cover (2 pcs.)
6
Holding angles (2 pcs.)
7
Sealing studs (2 pcs.)
8
Luster terminal, 4-pin (optional)
Surface mounting
Break out the required cable openings (1) on the rear
1.
panel (I or II).
If using the plastic rear panel (I), you also need to
2.
break out the mounting holes (2) on the rear side of the
rear panel.
3.
Mark the drilling points for the 3 mounting holes (2),
drill the holes and insert the dowels supplied.
4.
Pull the cables of the detector line and, where
applicable, the external supply, through the breakout
openings (1) on the rear panel (I or II).
Screw the rear panel tightly in place.
5.
Connect the cable to the terminal (3) in accordance
6.
with the connection diagram.
Hook the cover with (III) with the holes (4) over the
7.
cam-locks (5) on the rear panel.
8.
Push the cover (III) down over the holding angles (6),
press the sealing studs (7) upwards and fix the cover in
place by giving the sealing studs a quarter turn.
008860_i_--_--
2016-04-20

Werbung

loading

Diese Anleitung auch für:

Ft2011 seriesFt2010-a1Ft2010-c1Ft2011-a1