The transmitter can convert the input signal into a current or voltage
signal ("nominal output range"):
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
The start value adjusted for the measuring range (see page 39) is rep-
resented by the lower limit of the nominal output range. The adjusted
end value is represented by the upper limit of the nominal output
range. Within the usable signal range (see table below), the input
value is correctly represented by the output signal.
When the output signal lies outside the usable signal range, the
output signal is set to an error value (see illustrations on the following
page). This is signaled by the error LED.

Nominal Output Range

0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA

Measuring Ranges

A20210P0/0x
Usable Signal Range
0 ... 5.125 V
0 ... 10.25 V
0 ... 20.5 mA
3.8 ... 20.5 mA