Melder-relaissockel

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Figure 1: Terminal Layout
1
BREAK OUT TAB
5
FOR CURRENT
LIMITING
Figure 2a: 2-Wire System
Auxiliary Device Wiring
FROM CONTROL PANEL OR
PREVIOUS DEVICE
-
TO NEXT DEVICE
OR END OF LINE
2
3
1
4
5
+
Figure 2b: Typical 4-Wire System Connections
-
12/24V POWER SUPPLY
2
3
1
4
5
N/O
C
+
ALARM
MONITOR
Figure 3a: Tamper Resist
Activation
REMOVE TAMPER RESIST 'SNAP OFF' TAB
ON END OF PLASTIC ARM TO ENABLE
LOCKING OF SENSOR.
TABLE 2: ELECTRICAL RATINGS
Supply voltage dc
Standby Current
Contact activation time
after detector alarm
Contact reset time after
detector unlatch
Contact resistance
Contact rating dc
*Important - when a B324RL is to be used refer to the Breakout Tab
Option paragraph.
D350-01-00
B324RL, B312RL
INSTALLATION INSTRUCTIONS FOR 300 SERIES SENSOR RELAY BASES
SHORTING SPRING - PUSH
GENTLY IN THE DIRECTION
OF THE ARROW TO
ENGAGE; PUSH GENTLY
TOWARDS BASE TO
DISENGAGE
2
3
4
POSITION OF LED ON
SENSOR HEAD WHEN
MOUNTED (SINGLE LED
SENSORS)
TABLE 1: WIRING CONNECTIONS
Terminal
Function
No.
BASE TERMINALS
1
DO NOT USE
2
Supply In -
3
Supply Out -
4
DO NOT USE
5
Supply In and Out +
RELAY CONTACTS
TB1
Normally Open
C
N/O
TB2
Normally Closed
N/C
TB3
Common
2
3
1
4
5
N/O
C
Figure 3b: To Remove a
Locked Sensor
USE A SMALL SCREWDRIVER TO BREAK
THE INSET SECTION,
AND GENTLY PUSH
THE PLASTIC LEVER
IN THE DIRECTION OF
THE ARROW
B324RL
B312NL
B312RL
10.5 to 32V *
10-15V
10-15V
1µA
20µA
100ms
100ms
100ms
100ms
100ms
100ms
100mΩ
100mΩ
100mΩ
1A
1A
AND
GENERAL DESCRIPTION
These plug-in Sensor relay bases are for use with System Sensor 300
Series sensor heads (can also be used with obsolete 1151E/2151E
sensors). They are designed to operate in both 2 and 4-wire systems,
with screw terminals provided for power connections. Normally open and
normally closed relay contacts are provided on a separate terminal block.
The circuit built into the base provides current limiting to the sensor in the
alarm state.
The relay is controlled directly from the sensor, therefore as the sensor
is latched in alarm, so will be the base. For the B324RL and B312RL
latching relay bases, the alarm condition can only be terminated by
removal of the supply to the sensor and base. The B312NL Non-latching
base periodically isolates the sensor from the supply, hence providing an
"automatic reset" once the alarm stimulus has cleared.
SPECIFICATIONS
Base diameter:
Base height:
Weight:
Base fixing centres
Operating temperature range: -20°C to 70°C
Operating humidity range: 0 to 93% Relative Humidity (Non-condensing)
NOTE: In order to prevent possible nuisance alarms due to shock or
vibration, any devices connected to the B312RL base must not signal
an alarm until the relay base contacts have switched for a period greater
than 500mS.
MOUNTING
The sensor base should be mounted using pan head screws, with a
maximum thread diameter of 4mm, and maximum head diameter of
8mm. If required, suitable junction boxes may be used.
Sensor LED Position
If a single LED sensor is used, when mounted in the base the position of
its indicator LED will coincide with terminal 4 on the base.
WIRING
All wiring must be installed in compliance with applicable local codes and
standards, and the authority having jurisdiction.
See figure 2a if the base is to trigger an auxiliary device on a 2-wire
system, or figure 2b for connection to a 4-wire system.
The base terminals are designed to accept cables between 0.5mm² and
2.5mm², however reference should be made to the panel specifications
for acceptable cable resistance and capacitance. The NO/NC terminals
can accept multi core cables up to 1mm² or single core up to 1.5mm²
Note: Do not loop the wire under the terminals - to ensure supervision of
contacts, the wire run must be broken.
To permit continuity testing of the wiring circuit prior to installation of
END OF LINE
the sensor heads, the base contains a shorting spring which acts to
DEVICE
connect terminals 2 (negative in) and 3 (negative out) - see figure 1. To
activate, gently push the spring toward the centre of the sensor until it
clips into place. The short will automatically disengage when the sensor
is installed.
BREAKOUT TAB OPTION (B324RL ONLY)
See figure 1: When power to the B324RL is provided by a power supply
greater than 15V, without current limiting to 25mA or less in alarm, the
tab on the PCB should be broken using a suitable tool such as a pair of
thin nose pliers, otherwise damage may occur to the base and sensor.
Note: If in doubt, refer to the control panel manufacturer. Once broken
the tab cannot be reset!
Tamper Resist Feature
The base includes a feature which, when activated, prevents removal of
the sensor without a tool - see figures 3a and 3b.
1µA
1A
1
Pittway Tecnologica S.r.l., Via Caboto 19/3, 34147 Trieste, Italy
B312NL
127mm
29mm (excluding sensor)
96g (excluding sensor)
60mm
I 56- 1771- 020
E N G L I S H
I56-1771-020

Werbung

loading

Inhaltszusammenfassung für System Sensor 300 Serie

  • Seite 1 Figure 1: Terminal Layout GENERAL DESCRIPTION SHORTING SPRING - PUSH These plug-in Sensor relay bases are for use with System Sensor 300 GENTLY IN THE DIRECTION Series sensor heads (can also be used with obsolete 1151E/2151E OF THE ARROW TO sensors).
  • Seite 2 Si consiglia l'utilizzo di queste basi per relè per rilevatori plug in con testine DELICATAMENTE NELLA rilevatrici System Sensor Serie 300 (o della 1151E/2151E). Queste basi DIREZIONE DELLA FRECCIA sono state progettate per funzionare in sistemi a 2 e a 4 fili, con morsetti a PER ATTIVARE;...
  • Seite 3 Estas bases de detectores con relé se utilizan con detectores de la serie RESORTE DE CONTINUIDAD: EMPUJE SUAVEMENTE EN LA 300 (o 1151E/2151E) de System Sensor. Están diseñadas para funcionar DIRECCIÓN DE LA FLECHA en sistemas de 2 y 4 hilos, con terminales de tornillo para conexiones de PARA CONECTARLO;...
  • Seite 4 INSTALLATIONSANLEITUNG FÜR DIE MELDER-RELAISSOCKEL DER SERIE 300 Abbildung 1: Anschlussbelegung. ALLGEMEINE BESCHREIBUNG Der Sockel mit eingesetztem Relais wird in Verbindung mit System Sensor KURZSCHLUSS-METALLFEDER - Brandmeldern der Serie 300 (oder 1151E/2151E) eingesetzt. Die Sockel ZUR AKTIVIERUNG VORSICHTIG können in 2-Draht und 4-Draht Systemen eingesetzt werden und verfügen über IN PFEILRICHTUNG, ZUM Anschlussklemmen zur Spannungsversorgung.

Diese Anleitung auch für:

B324rlB312rlB312nl