Herunterladen Diese Seite drucken

ABB ESB Serie Montageanweisung Seite 5

Installationsschütz

Werbung

EN20..N
17.8
0.7''
EN40..N
54
2.13''
247C
IND.CONT.EQ
Use 75 °C Cu wire only:
ESB16/20 Main: 14 - 8 AWG / Torque 11 lb-in
ESB25 Main: 16 - 8 AWG / Torque 9 lb-in
ESB40/63 Main: 16 - 4 AWG / Torque 20 lb-in
ESB100 Main: 8 - 0 AWG I Torque 27 lb-in
Coil: 16 -10 AWG / Torque 8 lb-in
Suitable for use on a circuit capable of delivering not more than 5000 RMS
sym. amps, 240 V AC max. when protected: ESB16/20 by 20 A, K5 fuse
aym. amps, 480 V AC max, when protected:
ESB25 by 25 A, K5 fuse
ESB40 by 40 A, K5 fuse
ESB63 by 75 A, K5 fuse
ESB100 by 125 A, K5 fuse
ESB, EN
64.8
2.55''
2.4
2.09''
58
2.28''
6.8
0.27''
43.5
1.71''
58
2.28''
EN25..N
36
1.42''
EH04...N
9
0.35''
5
6.8
0.27''
43.5
1.71''
58
2.28''
6.8
0.27''
43.5
1.71''
58
2.28''
mm inch
2CDC103043M6801c / 02.2018

Werbung

loading

Diese Anleitung auch für:

En serieEsb16- n serieEsb20- n serieEn20- n serieEsb40- n serieEn25- n serie ... Alle anzeigen