4.6 Dimensions
Overview
Fig. 3 Dimensions
Note:
All dimensions in mm unless stated otherwise.
5

Installation Guidelines

5.1 Testing before set-up
WARNING!
Installation on non-level and non-structural
installation sites
Personal and property damage!
Ensure sufficient compressive strength according to
class C12/15 for concrete in the exposition class X0
according to EN 206-1.
Installation location has to be horizontal
Observe the weight
NOTICE
Sufficient noise insulation for the building is
ensured due the compact booster unit's safety
store.
NOTICE
Do not operate the compact booster unit near living
rooms and bedrooms.
Check the following points prior to installation:
Inspect the building architecture and prepare it
according to the dimension sheet.
According to specifications on the type label, the
system is suitable for the electric supply network.
Frost-free installation location
Lockable installation location
Well ventilated installation location
GB
A sufficiently dimensioned dewatering connection
(drain connection or similar) is required (observe
EN 12056).
If available, observe the creep resistance of the
compensator.
Compensators have to be able to be easily replaced.
5.2 Installation compact buster unit
WARNING!
The compact booster unit is top heavy.
Danger of injury of overturning of the compact
booster unit
Secure the system so that it cannot tip over before it
has been permanently anchored.
Anchor the system securely to the foundation.
To avoid the transfer of pipeline forces and structure-
borne sound to the compact booster unit, it is
recommended to install compensators with a tie bar.
Packaging is removed
Suitable location is selected according to specifications
For service work there is sufficient space in all directions.
1.
Mark the installation holes on the floor as desribed in
the data sheet.
2.
Drill holes (maximum Ø12 mm).
3.
Insert suitable, proper sized dowels.
4.
Position the system for installation.
5.
Anchor the system solidly to the foundation with
adequate bolts.