Herunterladen Inhalt Inhalt Diese Seite drucken

Special Conditions For Safe Use - MEDC XB15 Technisches Handbuch

Rundumblinkleuchte
Vorschau ausblenden Andere Handbücher für XB15:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5.0 SPECIAL CONDITIONS FOR SAFE USE

1. Painting and other surface finishes, other than those applied by the manufacturer, are not permitted
2. In order to maintain the dust tight integrity of the enclosures (IP6X), the threads of cable entry devices and
stopping plugs shall be sealed in accordance with the applicable code of practice for flameproof installation
6.0 CERTIFICATION/APPROVALS
IECEx units
Certified to IEC60079-0, IEC60079-1 and IEC61241-1-1
Ex d unit (IEC certification No. IECEx BAS 05.0048X)
Ex d IIC T
135°C (-55°C to +70°C)
A
T
100°C (-55°C to +55°C)
A
T
85°C (-55°C to +40°C)
A
The IECEx certificate and product label carry the IECEx equipment protection level marking
Ex d IIC
Dip A21 IP6X
Where Dip signifies suitability for use in the presence of dust
Where A21 signifies suitability for use in the presence of dust in a zone 21 area
ATEX units
Certified to EN50014, EN50018 and EN50281-1-1
EEx d unit (ATEX certification No. Baseefa04ATEX0009X)
EEx d IIC T135°C (-55°C to +70°C)
T100°C (-55°C to +55°C)
T85°C (-55°C to +40°C)
The ATEX certificate and product label carry the ATEX group and category marking:
II 2 GD
Where:
Signifies compliance with ATEX
II
Signifies suitability for use in surface industries
Signifies suitability for use in a zone 1 area
2
G
Signifies suitability for use in the presence of gases
D
Signifies suitability for use in the presence of dust
The ATEX certificate and product label also carry the following mark:
This signifies unit compliance to the relevant European directives, in this case 94/9/EC, along with the number of
the notified body issuing the EC type examination certificate.
© MEDC 2014
06/14

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis