Step 4: Connecting Electrical Loads Figure
Generator may only be loaded up to rated power under
the rated conditions as shown on unit data tag. Reduce
load when using generator outside of rated conditions.
Use only high quality, well-insulated extension cables in
accordance with IEC 245-4 with the generator's 230 Volt
AC outlets. Inspect extension cables before each use.
Check that all extension cables are suitably rated and
are not damaged. When using extension cords under 40°
C, the total length of cords for a cross section of 1.5 mm²
should not exceed 50 m or for a cross section of 2.5 mm²
should not exceed 80 m.
WARNING! Damaged or overloaded extension
cords could overheat, arc, and burn resulting in
death or serious injury.
• Electrical equipment, including cables and plug
connections, should not be defective.
230 Volt AC Receptacles
Use receptacles (R) to operate 230 Volt AC, single-phase,
50 Hz electrical loads. The receptacle is protected against
overload by a push-to-reset circuit breaker (K).
Protection of electrical components depends on circuit
breakers specifically matched to the generator. Replace
circuit breaker with identical rating and performance
characteristics.
WARNING! Generator voltage could cause
electrical shock or burn resulting in death or
serious injury.
• Do not touch bare wires or receptacles.
• Do not use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
• Do not operate generator in the rain or wet weather.
• Do not handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
• Do not allow unqualified persons or children to operate
or service generator.
• Keep children a safe distance from generator.
12 Volt DC Receptacle
The maximum current available for the 12 Volt DC
receptacle (G) is 60 Watts (5 Amps). A DC circuit
breaker (H) protects this receptacle from overloads. If an
overload occurs, the circuit breaker will trip (push button
pops out). Wait a few minutes and push the button in to
reset the circuit breaker.
This receptacle along with the USB adapter allows you to
recharge any USB powered device with a USB charging
cable (not included).
NOTICE For charging ITE (Information Technology
Equipment) only.
NOTICE When using this receptacle, push the QPT
switch to the OFF (0) position.
LED Panel
Figure
1
Output Indicator
The green LED output indicator light comes on when
the generator is operating normally. It indicates that the
generator is producing power at the receptacles.
Overload Alarm
The red LED overload alarm light comes on and cuts
power to the receptacles if you overload the generator.
The green output indicator light will also go off. If the
generator was overloaded, you must turn off and unplug
all electrical loads, then push the generator reset button
to continue operating.
Low Oil Indicator
The low oil indicator system is designed to prevent
engine damage caused by not enough engine oil. If the
engine oil level drops below a preset level, the yellow
LED low oil indicator light comes on and an oil switch will
stop the engine. If the engine stops or the yellow LED
low oil indicator light comes on when you pull the recoil
handle, check the engine oil level.

Parallel Operation

Two Briggs & Stratton inverter generators can be run
in parallel with a Briggs & Stratton parallel operation kit
(optional equipment). When running in parallel, the total
output of power is shown in chart.
Models
P2200 & P2200
P2200 & P3000
P3000 & P3000
NOTICE Total electrical load connected to the parallel
kit must not exceed the maximum output.
See the parallel operation kits instruction sheet for
detailed instructions on installation and operation of the
connected generators.
Step 5: Generator Shut Down
1. Turn off and unplug all electrical loads from generator
panel receptacles. Never stop engine with electrical
devices plugged in and turned on.
2. Let engine run at no-load for one minute to stabilize
internal temperatures of engine and generator.
3. Push engine switch to OFF (0) position.
7
Maximum Output
3000 Watts
3000 Watts
4800 Watts
7