General regulations
General Regulations
Data Plate
Data plate
Operating principle
1
2
3
4
5
6
7
8
9
Operating principle
The TRIGON XL is a fully modulating
boiler.
The control unit of the boiler adapts
the modulation ratio automatically
to the heat demand requested by
the system. This is done by control-
ling the speed of the fan. As a result,
the mixing system will adapt the gas
ratio to the chosen fan speed, in
order to maintain the best possible
combustion figures and therewith
the best efficiency.
The flue gases created by the com-
bustion are transported downwards
8
Symbols used on the data plate
Symbols used on the data plate
1
3
S/N
0000000KE000000000000
8
9
12
13
=
η
11
100%
gas
mbar
gas
mbar
gas
mbar
Brand
Country of origin
Boiler model - Serial number
Commercial reference
Certification number
Destination country
- Gas category
Gas setting
Installation type
Electrical data
0000000KE000000000000
through the heat exchanger and
leave the boiler at the bottom into
the chimney connection.
The return water from the system
enters the boiler in the lower sec-
tion, where is the lowest flue gas
0000000KE000000000000
temperature in the boiler.
The water is being transported up-
wards through the heat exchanger,
in order to leave the boiler at the
flow connection. The cross flow
working principle (water up, flue gas
down) ensures the most efficient
combustion results.
4
26-05-2015
5
10
6
7
MAX
MIN
14
Q(Hi)
15
P
60/80C
P
30/50C
=
η
min.
16
10
Factory settings
11
Maximum water pressure
12
Boiler type
13
NOx class / Efficiency
14
Input rating nominal heating
15
Power output heating
16
Gases which may be used
17
Ambient operating temp.
18
Max. central heating temp.
2
Legend :
00
1
2
3
4
5
6
7
8
9
10
17
11
18
12
13
14
15
16
17
18
The LMS14 control unit can control
the boiler operation based on:
• Boiler control
(stand alone operation);
• weather compensated operation
(with optional outdoor sensor);
• with 0-10V external influence
(temperature or capacity) from a
building management system.
Brand
Country of origi
Boiler model - S
Commercial ref
Certification nu
Destination cou
Gas setting
Installation type
Electrical data
Factory settings
Maximum wate
Boiler type
NOx class / Effi
Input rating nom
Power output h
Gases which m
Ambient operat
Max. central he
6
5
4
3
2
PCT