T
ECHNICAL DATA TABLE
MODELS
INPUT (3 Ø + N star-configured voltages)
Nominal voltage
Accepted range
Voltage range for non-intervention of
battery
Nominal frequency
Maximum current (1)
Nominal current (2)
Power factor
Current distortion @ max load
BYPASS (on L1)
Voltage range accepted for switching
Frequency range accepted for switching
Switching time
BATTERY
Recharge time (8)
OUTPUT
Nominal voltage
Static variation (3)
Dynamic variation (4)
Waveform
Voltage distortion @ linear load
Voltage distortion @ distorting load
Frequency (5)
Current crest factor
Nominal power (VA)
Nominal power (W)
Short circuit current
SUNDRY
Leakage current to earth
AC/AC performance
Ambient temperature (6)
Humidity
Protections
Hold-up time
Noise
Dimensions H x L x D (mm)
Weight in Kg (estimated)
(1) @ nominal load, minimum voltage of 180Vac, battery charging
(2) @ nominal load, nominal voltage of 230Vac, battery charging
(3) Mains/Battery @ load 0% -100%
(4) @ Mains/battery/mains @ resistive load 0%/100%/0%
(5) If the mains frequency is within ±5% (user definable) of the selected value, the UPS is synchronized with the mains. If the
frequency is out of tolerance or in operation from battery, the frequency is the selected value ±0.1%
(6) 20 - 25 °C for extended battery life
(7) Recalibration may be necessary after a long period of operation, in order to maintain the output voltage within the indicated
range.
(8) Time needed to reach 90% of charge (after a full discharge at load ≥80%)
64
SPT 6500
220 – 230 – 240 Vac single-phase / 380 – 400 – 415 Vac three-phase
Maximum voltage 276Vac
from 184 to 138 Vac from 100% to 50% of the linear load
Return of operation from mains at 190Vac
12
8
 6% single-phase /  26% three-phase
Frequency selected ±5%
220/230/240 Vac selectable ±1.5%
50 o 60 Hz selectable
6500
5200
1.5 x In for t= 0.5sec
< 90% non condensing
excessive battery discharge - overcurrent - short circuit - overvoltage -
undervoltage - thermal
615mm x 282mm x 785mm
91 Kg
SPT 8000
with neutral
0 - 280 Vac
Minimum voltage:
50 - 60 Hz ±5Hz
14
10
 0.95
180 - 264 Vac
0.1ms
6-8 h
1.5% (7)
 5% in 20ms
Sinusoidal
 3%
 6%
 3 : 1
8000
6400
 10mA
92%
0 – 40 °C
 40msec
< 45 dB(A) at 1mt.
94 Kg
SPT 10000
17
12
10000
8000
95 Kg