5. MAINTENANCE

Attention: before handling and/or opening the access panels it is compulsory to shut down the power supply
using the general switch located on the front panel. If options KWin and\or KWout are installed, then shut down the
corresponding general switches.
Regular maintenance of the HRg unit is essential to guarantee a good operation of the device and a long life
expectancy. The maintenance frequency will depend on the application and on the actual environment conditions
but in a general way the following controls are advised:

5.1. Once the unit operates in normal condition

Replace the starting filters kit by a kit for replacement filters. See Section 1.4 of this booklet.

5.2 Every 3 months

1.
Check for any alarm indicated on the control device. In case of alarm refer to control manual.
2.
Check the state of filter clogging. The control device allows to set a pre-defined 'filter clogging' threshold (refer
to installation manual). If need be replace filters. Filters that are too clogged can generate the following
problems :
Insufficient ventilation
Excessive increase of fan rotation speed, creating excessive sound level
Excessive power consumption (power consumption will increase exponentially to an increase in pressure
drop, for a constant airflow)
A damaged filter allows unfiltered air to enter heat exchanger (risk of clogging) and into ventilated room.
List of replacement filters :
Filters dimensions
Unit type
HRg 800
HRg 800 ECO
HRg 1200
HRg 1200 ECO
HRg 2000
HRg 2000 ECO
HRg 3000
HRg 3000 ECO
HRg 4000
HRg 4000 ECO
HRg 5000
HRg 5000 ECO
HRg 6000
HRg 6000 ECO
3.
Inspection and cleaning of the inside of the unit:
- Vacuum clean any accumulation of dust in the unit.
- Inspect and gently vacuum clean if need be the heat exchanger. Use brush accessory to protect fins.
- Clean the possible condensation marks and possible accumulations in the drain pan.

5.3 Every 12 months

1.
Check for any alarm indicated on the control device. In case of alarm refer to installation manual.
2.
Check the state of filter clogging. The control device allows to set a pre-defined 'filter clogging' threshold (refer
to installation manual). If need be replace filters. Filters that are too clogged can generate the following
problems :
Insufficient ventilation
Excessive increase of fan rotation speed, creating excessive sound level
Filter on
[mm]
supply air
470x287x50
1 x F7
830x287x50
1 x F7
503x370x50
2 x F7
1 x 503x370x50
3 x F7
2 x 436x370x50
436x370x50
4 x F7
503x370x50
5 x F7
503x370x50
5 x F7
36
Filter on
Filters kit (supply+exhaust)
exhaust air
1 x M5
1 x F7
1 x M5
1 x F7
2 x M5
2 x F7
3 x M5
3 x F7
4 x M5
4 x F7
5 x M5
5 x F7
5 x M5
5 x F7
CID
510089
510072
510090
510073
510091
510054
510092
510074
510093
510056
510094
510058
510094
510058