1.4 Filters

The heat recovery ventilation unit is equipped with M5 class filters at the inlet of the polluted air and F7 class filters
at inlet of the fresh air, to correctly protect the heat exchanger and guarantee optimum air quality inside the
building. However, the unit is originally delivered with a G4/F7 starter kit of filter. Once the unit has been running
for a few weeks, filters need to be replaced by a M5/F7 filters kit. F7 filters on both sides (supply & exhaust) are
available as an additional option.
Filters are the protectors of the heat exchanger, but also of the quality of the air you breathe. Check regularly
(once a month) the state of the filters. Vacuum the filters if necessary, and replace them when they are too dirty.
Clogged filters can create the following failures:
- Insufficient ventilation
- Excessive increase of the rotation speed of the fan creating excessive noise and power consumption
- A damaged filter allows 'dirty' air to enter the heat exchanger which will eventually clog the heat exchanger
Filter identification for replacement:
Filters dimensions
Unit type
HRg 800
HRg 800 ECO
HRg 1200
HRg 1200 ECO
HRg 2000
HRg 2000 ECO
HRg 3000
HRg 3000 ECO
HRg 4000
HRg 4000 ECO
HRg 5000
HRg 5000 ECO
HRg 6000
HRg 6000 ECO
1.5 Installation control datasheet (see appendix)
When the installation is completed and running, we strongly advise that the installer fills in the installation
datasheet recapitulating all the data useful for maintenance of the installation. Please keep a copy of this
datasheet close by as it may come handy for many reasons:
make a clear communication in case of discussion with the manufacturer
information if you need to change parameters when necessary,
this document can become an important factor in case of guarantee issues.

1.6 Warranty

The warranty of the manufacturer begins at the date of invoicing of PLC to the installer. The warranty is of 2 years,
except on the mobile parts where it is of 1 year.
The warranty is limited to the replacement of the defective parts, and does not include labor and traveling
expenses. The warranty becomes void if:
The installation is not accomplished according to the prescriptions described in this above.
Repairs were carried out by unqualified staff.
The startup control datasheet (see appendix) is not filled in properly and not made available when claiming

1.7 Conformity

CE, under formal condition that the final product integration is made in conformity with the applicable
standards.
Eco design (Directive 2009/125 / EC) - LOT 6 (1253/2014). See details on our website: www.lemmens.com.
Filter on
[mm]
supply air
470x287x50
1 x F7
830x287x50
1 x F7
503x370x50
2 x F7
1 x 503x370x50
3 x F7
2 x 436x370x50
436x370x50
4 x F7
503x370x50
5 x F7
503x370x50
5 x F7
Filter on
Filters kit (supply+exhaust)
exhaust air
1 x M5
1 x F7
1 x M5
1 x F7
2 x M5
2 x F7
3 x M5
3 x F7
4 x M5
4 x F7
5 x M5
5 x F7
5 x M5
5 x F7
29
CID
510089
510072
510090
510073
510091
510054
510092
510074
510093
510056
510094
510058
510094
510058

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis