Herunterladen Inhalt Inhalt Diese Seite drucken

Schematic Of The T° Sensors Positioning In The Hrg Units; Power Supply To The Fans And The Control Devices; Power Supply For The Electrical Antifreeze Protection Coil Kwin (Option) - Auerhaan HRglobal TAC5 Installations- Und Wartungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3.1.2 Schematic of the T° sensors positioning in the HRg unit
To allow easier identification of the temperature sensors 4 different wire colors are used:
-
T1 : black wire
-
T2 : white wire
-
T3 : blue wire
-
T4 & T5 : green wire

3.2 Power supply to the fans and the control devices

All the internal cables (fans, controls, sensors, ...) to the main switch are factory pre-wired. All the power supply
wiring that remains is the main power supply to the main switch(es).
Wiring specifications:
Unit type
HRglobal 800
HRglobal 800 ECO
HRglobal 1200
HRglobal 1200 ECO
HRglobal 2000
HRglobal 2000 ECO
HRglobal 3000
HRglobal 3000 ECO
HRglobal 4000
HRglobal 4000 ECO
HRglobal 5000
HRglobal 5000 ECO
HRglobal 6000
HRglobal 6000 ECO
(1) Grounding is compulsory
(2) D type "slow" reaction curves - shutoff power 10.000A - AC3.
(3) Max current is reached in the neutral.
(4) 3x400V + N.

3.3 Power supply for the electrical antifreeze protection coil KWin (option)

All the internal cables of the KWin coil to the main switch are factory wired. All that needs to be wired is the main
power supply to the main switch.
Wiring specifications:
Unit type
HRglobal 800
HRglobal 800 ECO
HRglobal 1200
HRglobal 1200 ECO
HRglobal 2000
HRglobal 2000 ECO
HRglobal 3000
HRglobal 3000 ECO
HRglobal 4000
HRglobal 4000 ECO
HRglobal 5000
HRglobal 5000 ECO
HRglobal 6000
HRglobal 6000 ECO
Supply
Maximum amps
Voltage (1)
1 x 230V
5,5 A
1 x 230V
5,2 A
1 x 230V
7,0 A
1 x 230V
5,2 A
1 x 230V
14,3 A
1 x 230V
11 A
1 x 230V
17,8 A
1 x 230V
11,2 A
3 x 400V + N
18,0 A (3)
1 x 230V
13,2 A
3 x 400V + N
18,0 A (3)
3 x 400V + N
5,8 A
3 x 400V + N
23,1 A (3)
3 x 400V + N
5,8 A
Supply
KWin heating
voltage
capacity
3 x 400V + N
3 kW
3 x 400V + N
6 kW
3 x 400V + N
6 kW
3 x 400V + N
9 kW
3 x 400V + N
12 kW
3 x 400V + N
18 kW
3 x 400V + N
18 kW
Protection type (2)
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
D – 10.000A – AC3
Maximum amps
4,3 A
8,7 A
8,7 A
13,0 A
17,3 A
26,0 A
26,0 A
33
Protection caliber
8A
8A
8A
8A
16A
16A
20A
16A
20A (4)
16A
20A (4)
8A
25A (4)
8A

Werbung

Inhaltsverzeichnis
loading