Mounting instructions
Positioning
In main living room, on an inside wall: not exposed to
sun or other foreign heat sources (chimny wall, near
radiators, draughts, televisions, lamps); not hidden
by furniture, or curtains; ca. 1.2-1.5m above the floor;
due to draughts seal installation conduit.
Dimensions
-3
+3
8
85
The housing floor can be used as a stencil for boring
holes.
The cover can be opened by depressing
the strap with a screwdriver (on the right
side of the wall, in the middle).
Installation
Allowable cable length is max. 50m for > 0.25mm
wire. Avoid running the cable parallel to the main
(230VAC)
power
supply
disturbances/protective insulation). If possible use a
2 wire cable (not two individual wires). Avoid conduit-
or connector-box.
Hint:
If a room sensor is connected, do not install a thermal
valve in the reference room.
RFB410A
Scheme
7 20
2
cable
(electrical
loading