Operation instructions
RFB410A
162406/04.13
Remote control with Party- and Savings-function as
well as correction of room temperature.
Correction of room temperature
Correcting the room temperature set
value by
+3°C.
(temperature "normal" and "reduced")
-3
+3
Changing the operation mode (under cover)
Set the switch to the desired operating
condition:
Prolonged "reduced" or "frost
protection" (saving-function):
The room set value for prolonged "reduced"
or "frost protection" is active according to the
controller setting.
Automatic: Heating according to controller
setting (controller operating mode).
Prolonged "normal" (party-function): Reduced
values programed in the controller will be ignored
(room set value, prolonged "normal"). Hot water loa-
ding will no longer be influenced by the remote control.
The following controller operating modes can not be
adjusted from the remote control unit: "Hand",
"Standby" and "Summer". These operating modes
can be activated on the controller itself, or partially
through an external switch.
Influence of room sensor:
A variation between the room set value temperature
and the measured room temperature, will result in an
increase or a decrease of the flow
temperature. If no room sensor is
desired, it can be deactivated (with
X1
pliers cut bridge X1).
Influence °C room temperature variation on flow
temperature (S=slope on controller):
a) Outside temperature regulated control system:
(example:
S=0.7 -> 3.2°C ¦ S=1.3 -> 4.3°C)
b) Room temperature regulated system:
(no outside sensor connected to controller)
(example:
S=0.7 -> 10°C ¦ S=1.3 -> 14°C)